Valve Control Configuration - Siemens SITRANS FC330 Operating Instructions Manual

Coriolis flowmeters
Table of Contents

Advertisement

Parameter assignment
8.2 Functions
8.2.8.2

Valve control configuration

Valve control dosing
Dosing is controlled with either one or two discrete valves or a single analog valve. The
transmitter provides up to three input/output channels which can be used for dosing control.
The selection of channels is fixed when ordering the system. The channels can be setup for
dosing functionality in parameter 2.5.1 "Dosing Mode" as shown in the table below. Allocation
of the output to a specific dosing sequence element is performed in the software configuration
as follows:
One on/off valve
Configuration of one valve (primary valve).
One of the following channels must be assigned to control the discrete primary valve.
Table 8-1
One on/off valve
Valve control
Channel HW con‐
figuration
Discrete valve con‐
Signal output
trol - Primary Valve
Relay output
Two on/off valves
Configuration of two valves (primary and secondary valves)
148
Output
Channel SW configuration
channel
Menu item
2
2.4.2.1
2.4.2.27
3
2.4.3.1
2.4.3.29
4
2.4.6.1
2.4.6.27
3
2.4.4.1
4
2.4.7.1
"Operation Mode"
"Status Mode"
"Operation Mode"
"Status Mode"
"Operation Mode"
"Status Mode"
"Status Mode"
"Status Mode"
Operating Instructions, 01/2019, A5E44030648-AB
Value
Status Output
Primary Valve Dosing
Status Output
Primary Valve Dosing
Status Output
Primary Valve Dosing
Primary Valve Dosing
Primary Valve Dosing
SITRANS FC330