Attach The Intake Grille; Optional Installation Work; Optional Kit Installation; External Input And Output - Fujitsu AUXG-KVLA Series Installation Manual

Compact cassette type
Table of Contents

Advertisement

(2) Connect the connector.
Cable (louver): WHITE
• Arrange the cables as illustrated below.
(3) Attach the connector cover.

4.3. Attach the intake grille

The installation is the reverse of "REMOVING THE INTAKE GRILLE".
The intake grille can be rotated and installed 4 ways to suit the user's preference.
• The louver angle cannot be changed if the power is not on. (If moved by hand, it may
be damaged.)
• The grille assembly is directionally relative to the air conditioner body.
• Install so that there is no gap between the grille assembly and the air conditioner
body.
• The cassette grille equips with an accessory to prevent the grill completely open.
Be sure to read the INSTALLATION SHEET included with the cassette grille before
installation.

5. OPTIONAL INSTALLATION WORK

5.1. Optional kit installation

Regulation of cable differs from each locality, refer in accordance with local rules.
CN47 CN65
Remote controller cable
This air conditioner can be connected with the following optional kits.
For details on how to install optional parts, refer to the installation manual included in each
item.
Connector No.
CN46
CN47
Fresh air intake kit (UTZ-VXAA) External output (UTY-XWZXZG) [*1]
CN65 [*2]
*1: For external output terminal setting, refer to Function No.60 in "7. FUNCTION SET-
TING".
En-12
Cable (display): WHITE
Cable (louver): RED
Indoor unit side
Screw
Connector cover
CAUTION
WARNING
CN46
Terminal (External input)
Option type
Wired remote controller
External input (PCB Terminal)
Other optional parts
*2: Other options (WLAN adapter, converters, etc.) may be connectable. Please refer to
the technical data for details.
NOTES: Options connecting to CN47 or CN65 cannot be used at the same time.

5.2. External input and output

5.2.1. External input
• Indoor unit functions such as Operation/Stop or Forced stop can be done by using
indoor unit terminals.
• "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of
indoor unit.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m (492 ft.).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Y1
TO REMOTE CONTROL UNIT
● Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal.
*1
Connected device
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
■ Operation behavior
● Input signal type
ON
Edge
OFF
When function setting is "Operation/Stop" mode 1.
Input signal
OFF → ON
Operation
ON → OFF
Stop
When function setting is "Forced stop" mode.
Input signal
OFF → ON
Forced stop
ON → OFF
Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
When function setting is "Operation/Stop" mode 2.
Input signal
OFF → ON
Operation
ON → OFF
Stop (R.C. disabled)
Terminal
Y2
Y3
1
2
Ex IN
Connected device
Terminal
(External in)
Command
Command
Command