Parameterizing the SITOP UPS1600

The following examples show you how the uninterruptible SITOP UPS1600 power supply is
parameterized:
● Buffering an S7 IO controller, including the I/O when the power fails
● Switching off the UPS when the power fails by a user program
Parameterizing the uninterruptible SITOP UPS1600 power supply for additional tasks,
please refer to the UPS1600 Manual.
6.1

Buffering an S7 IO controller, including the I/O when the power fails

Preconditions
● STEP 7 V12 has been started and a project with an S7 IO controller and SITOP
● The hardware has been completely wired up.
Assigning parameters
Note
If you click in the entry fields, the value range is displayed that you can enter.
1. Double-click in the network view on the UPS1600 to display it in the device view.
2. Click in the device view of the UPS1600 to select it.
3. In the inspector window click on the "Properties" and "General" tab.
SITOP UPS1600 under STEP 7 V12
Getting Started,
UPS1600 has been created.