Integrate the meter with the control system
June 2019
Channel
Channel C
Channel D
Restriction
You cannot configure Channel Type for Channel A and Channel B. Channel A is always mA Output 1.
Channel B is always mA Output 2.
Postrequisites
For each channel that you configured, perform or verify the corresponding output configuration. When the
configuration of a channel is changed, the channel's behavior will be controlled by the configuration that is
stored for the selected output type, and the stored configuration may not be appropriate for your process.
After verifying channel and output configuration, return the control loop to automatic control.

8.2 Configure an mA Output

Use an mA Output to report current values of process variables. The mA signal varies between 4 mA and
20 mA in proportion to the current value of the assigned process variable.
Depending on your purchase order and channel configuration, your transmitter may have 1-2 mA Outputs.
Channel A is always mA Output 1, and Channel B is always mA Output 2.
Note
Channel A also supports HART/Bell 202 communications, superimposed on the mA signal. HART is not
available on Channel B or Channel C.
8.2.1 Configure mA Output Source
Menu → Configuration → Inputs/Outputs → Channel x → I/O Settings → Source
Display
Device Tools → Configuration → I/O → Outputs → mA Output x
ProLink III
Field Communicator
Configure → Manual Setup → Inputs/Outputs → Channel x → mA Output x → mAOxSource
mA Output Source specifies the process variable that is reported by the mA Output.
Prerequisites
If you plan to configure the output to report volume flow, ensure that you have set Volume Flow Type as
desired: Liquid or Gas Standard Volume.
If you plan to configure an output to report a concentration measurement process variable, ensure that
the concentration measurement application is configured so that the desired variable is available.
If you are using the HART variables, be aware that changing the configuration of mA Output 1 Source will
change the configuration of the HART Primary Variable (PV).
128
Options
mA Output 3
Frequency Output 1 (default)
Discrete Output 1
Frequency Output 2
Discrete Output 2 (default)
Micro Motion 5700 Transmitters with Intrinsically Safe Outputs
Configuration and Use Manual
MMI-20039472