Monitor Parameters - Toshiba TOSVERT VF-AS3 Instruction Manual

Embedded ethernet function
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Comm.
Title
No.
C682
C682
(*1): These parameters are affected after reset. Wait 5 second from the setting to reset to ensure that settings
are reflected.
If you want to change the IP address and the device name, please set the device name first.
(*2): The unit is depended by the [F519] setting.
(*3): In the CPU1 version V104 or earlier of VF-AS3, parameter value 14 is reserved for internal process.
Do not set the <C670> at 14 with V104 or earlier, inverter initialization cannot be completed after reset.
(*4): This parameter is supported in the CPU1 version V114 or rater.

2.3. Monitor parameters

The following parameters can be used for network status confirmation of the embedded ethernet.
Comm.
Title
No.
C623 to
C623 to
C628
C628
C629 to
C629 to
C632
C632
C633 to
C633 to
C636
C636
C637 to
C637 to
C640
C640
C696
C696
C697
C697
C698
C698
C699
C699
Parameter name
EmbEth. Inverter to
inverter communication
(*1) (*4)
Parameter name
Emb Eth. MAC address monitor
Emb Eth. IP address monitor
Emb Eth. Subnet mask monitor
Emb Eth. Default gateway monitor
Emb Eth. Command monitor
Emb Eth. Frequency command
monitor
Emb Eth. Error monitor
Emb Eth. External error monitor
Description
0: Follower (0Hz command when Leader fails)
1: Follower (continue running when Leader fails)
2: Follower (emergency off when Leader fails)
3: Leader (transmit frequency command)
4: Leader (transmit output frequency signal)
5: Leader (transmit torque command)
6: Leader (transmit output torque command)
The MAC address of the device.
[C623 – C624 – C625 – C626 – C627 – C628]
The current IP address of the device.
The subnet mask actual of the device.
The gateway IP address actual of the device.
This parameter displays the command from
Embedded Ethernet.
This parameter displays the reference frequency from
embedded ethernet.
Monitor of the Ethernet error.
0: No error
1: Modbus TCP Scanning timeout
3: INV to INV communication timeout
4: EtherNet/IP timeout
5: Modbus Message timeout
Monitor of the Ethernet error.
0: No error
1: Invalid IP address
2: Duplicate IP address
3: INV to INV communication configuration error
10