CPU 210 Data Sheets
A.1

General Technical Specifications

National and International Standards
The national and international standards listed below were used to determine appropriate
performance specifications and testing for the S7-200 family of products. Table A-1 defines
the specific adherence to these standards.
Underwriters Laboratories, Inc.: UL 508 Listed (Industrial Control Equipment)
Canadian Standards Association: CSA C22.2 Number 142 Certified (Process Control
Equipment)
Factory Mutual Research: FM Class I, Division 2, Groups A, B, C, & D Hazardous
Locations, T4A
VDE 0160: Electronic equipment for use in electrical power installations
European Community (CE) Low Voltage Directive 73/23/EEC
EN 61131-2: Programmable controllers - Equipment requirements
European Community (CE) EMC Directive 89/336/EEC
Electromagnetic emission standards:
EN 50081-1: residential, commercial, and light industry
EN 50081-2: industrial environment
Electromagnetic immunity standards:
EN 50082-2: industrial environment
Technical Specifications
The S7-200 CPUs and all S7-200 expansion modules conform to the technical specifications
listed in Table A-1.
Table A-1
Technical Specifications for the S7-200 Family
Environmental Conditions — Transport and Storage
IEC 68-2-2, Test Bb, Dry heat &
IEC 68-2-1, Test Ab, Cold
IEC 68-2-30, Test Db, Damp heat
IEC 68-2-31, Toppling
IEC 68-2-32, Free fall
Environmental Conditions — Operating
1
Functional range
IEC 68-2-14, Test Nb
IEC 68-2-27 Mechanical shock
IEC 68-2-6 Sinusoidal vibration
EN 60529, IP20 Mechanical protection
A-2
-40 C to +70 C
25 C to 55 C, 95% humidity
100 mm, 4 drops, unpacked
1 m, 5 times, packed for shipment
0 C to 55 C, 95% maximum non-condensing humidity
5 C to 55 C, 3 C/minute
15 G, 11 ms pulse, 6 shocks in each of 3 axis
0.35 mm peak-to-peak 10 to 57 Hz; 2 G panel mount, 1G din rail mount,
57 to 150 Hz; 10 sweeps each axis, 1 octave/minute
Protects against finger contact with high voltage as tested by standard
probes. External protection is required for dust, dirt, water, and foreign
objects of less than 12.5 mm in diameter.