Prerequisites
Export plant diagram
from ACS790
Import plant diagram to
web server
60 / 102
Siemens
Building Technologies
4.5

Import web-capable plant diagrams

• The drafter is logged on to the web server as an administrator.
• Web server is connected with the bus with one or more bus devices.
• The devices web page for the bus device is generated per Section 2.4. The web
server menu tree and data point information for the controller is now available.
Procedure on ACS790:
• Select bus device.
• Copy standard diagram and re-add to the same bus device (standard diagram
cannot be exported).
The copied icon is light blue.
• Rename diagram.
• Export diagram using the "Export to..." function.
In the data type dialog field, select *.tar and save.
Workflow on web server:
1. Start at the home node in secondary navigation for the desired bus.
2. Click Import.
The import dialog ("file name (*.tar)") is displayed.
3. "Search..." to go to the .tar file saved on the computer.
4. Click Open.
5. Click Upload.
Import information is displayed while the file is being read; the property
dialog box now opens.
6. Check replacement function with "Replace datapoint addresses".
7. From the dropdown list box, select the bus address for the connected
controller.