Test condition
LAN
Internet
Test message receiver
Note
36 / 102
Siemens
Building Technologies
2.7

Functional check

Connections must be tested if all settings were made to the web server as well as
to system devices.
A PC on the local network is used to test operations via LAN. The log in dialog
box must be displayed after entering the local IP address for the web server
(see Section 2.2.2).
We recommend using mobile participants with Internet access (Smart phone,
mobile phone) to test operation over the Internet. The login dialog box must be
displayed after entering the public IP address or plant domain (see Section 0).
Do the test if the web server is to send a message or system report via e-mail
for a fault.
The test is also carried out if message suppression is switched on.
Path: Home > 0.5 OZW672... > Settings > Message receiver
Data point
Test message receiver
Default val:
---
Setting val:
Message receiver
1..4
System report sent
Display values: ---, Yes, No
Cause
Display values: ---, Network cable,
DNS setting, Address mail server,
Port number mail server, E-mail
address receiver, Authentication
mail server.
Message inhibition
Display values: Yes, No
Web server
Commissioning
Explanation, example
Select a message receiver to test the con-
nection to the receiver.
The display changes from "
few seconds. Message sent successfully.
No: Message receiver not reached.
"Cause" displays the results of "System
report sent".
For "Yes" the cause is "---"
For "No" the cause is displayed.
The first fault is displayed for multiple faults.
Shows the message suppression switch
setting (8) (see Section 1.2).
" to "Yes" after a
---