Electrical Data Table - Carrier 38AUM Series Installation, Operation & Maintenance Manual

Air cooled condensing units–50hz
Table of Contents

Advertisement

ELECTRICAL DATA TABLE

Single Circuit Unit - 400V-3Ph-50Hz
VOLTAGE RANGE
Unit
MIN
38AUMZ07
360
38AUMZ08
360
Dual Circuit Unit - 400V-3Ph-50Hz
VOLTAGE RANGE
V-Ph-Hz
MIN
38AUMD12
360
38AUMD14
360
38AUMD16
360
Legend and Notes for Electrical Data Table
FLA - Full Load Amps
IFM - Indoor (Evaporator) Fan Motor
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Overcurrent Protection
Application heater kW (Using multiplication factor table in Electric Resistance Heater Data Table)
Unbalanced 3-Phase Supply Voltage
Never operate a motor where phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percentage of voltage imbalance
Maximum Deviation From Average Voltage
= 100 X
Example: Supply Voltage is 400V - 3ph - 60Hz
AB = 392v
Average Voltage =
BC = 404v
AC = 395v
=
Determine maximum deviation from average voltage.
(AB) 397 - 392 =5v
(BC) 404 - 397 =7v
(AC) 457 - 397 =2v
Maximum Deviation is 7v.
Determine Percentage Voltage Imbalance.
% Voltage Imbalance
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
COMP 1
MAX
RLA
LRA
440
9.7
64
440
12.2
100
COMP 1
MAX
RLA
LRA
440
7.8
51.5
440
10.6
74
440
12.2
101
Average Voltage
392 + 404 + 395
3
1191
= 397V
3
7
= 100 X
397
COMP 2
RLA
LRA
-
-
-
-
COMP 2
RLA
LRA
7.8
51.5
10.6
74
12.2
101
NEC - National Electrical Code
OFM - Outdoor (Condenser) Fan Motor
RLA - Rated Load Amps
HACR - Heating, Air-Conditioning and Refrigeration
◊ Fuse or HACR Circuit Breaker
= 1.76%
Page 30
OFM (ea)
POWER SUPPLY
HP
FLA
MCA
1/4
0.7
13.5
1/3
1.8
18.9
OFM (ea)
POWER SUPPLY
HP
FLA
MCA
1/3
1.8
21.2
1/3
1.8
27.5
1/2
1.7
30.9
MOCP
20
30
MOCP
25
35
40