Required Condition - Samsung DVM S AM100MXVDGH/ET Technical Data Book

Vrf, dvm s for euro_et (r410a, 50hz, hp)
Hide thumbs Also See for DVM S AM100MXVDGH/ET:
Table of Contents

Advertisement

10. Installation
Refrigerant pipe installation
Electrical wiring work
EEV kit
EEV kit ~
Actual pipe
Indoor unit
length
❇ Please refer to the EEV Kit manual.
Note 1) Required condition
Classification
First branch joint ~
Farthest Indoor unit
Total length of
extended pipe
Each Y-joint ~
Each indoor unit
Difference between the distance of the outdoor unit to the farthest
indoor unit and nearest indoor unit ≤ 45m, (a+b+c+d+e+g+p)-(a+h) ≤ 45m
Note 2) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m, (If the height
difference is over 40m, contact your local dealer for more information.)
but when the indoor unit is located at lower level than outdoor unit, allowable height difference is 110m
(If the height difference is over 50m, need to decide whether to install PDM kit or not.)
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
70
2 m
20 m or less
Condition
45m ≤ b+c+d+e+f+g+p ≤ 90m: branch pipes (b, c, d,
e, f, g) size must be increased by 1 grade
If the size of pipe (main pipe), between the first
branch joint and the outdoor unit, is not increased
by 1 grade, a+(b+c+d+e+f+g)×2 +h+i+j+k+l+m+n+p
≤ 1000 m
If the size of pipe (main pipe), between the first
branch joint and the outdoor unit, is increased by
1 grade, (a+b+c+d+e+f+g)×2 +h+i+j+k+l+m+n+p ≤
1000 m
h, i, j, ... p ≤ 45 m
Model name
MEV-E24SA
MEV-E32SA
MXD-E24K132A
MXD-E24K200A
MXD-E32K200A
MXD-E24K232A
MXD-E24K300A
MXD-E32K224A
MXD-E32K300A
1 indooor
2 indooor
Apply to products without EEV
(Wall mount & ceiling)
3 indooor
Example
Remarks

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents