Samsung DVM S AM100MXVDGH/ET Technical Data Book page 74

Vrf, dvm s for euro_et (r410a, 50hz, hp)
Hide thumbs Also See for DVM S AM100MXVDGH/ET:
Table of Contents

Advertisement

10. Installation
Refrigerant pipe installation
Installing the MCU
MCU specification
Model
Exterior of MCU
Number of
connectable indoor
units at one port
The maximum
capacity of the
connectable indoor
units at one port
The maximum
capacity of the
connectable indoor
units
Internal EEV
• Indoor units without internal EEV(AM∗∗∗∗NTDE∗, AM∗∗∗∗NADE∗) can not be connected directly to the
MCU.
CAUTION
• Please connect these indoor units using EEV kit(MEV-E∗∗SA, MXD-E∗∗K∗∗∗A).
74
MCU-S6NEK2N
Up to 8 units
16 kW
61.6 kW
MCU-S4NEK3N
MCU-S2NEK2N
Up to 8 units
16 kW
61.6 kW
Not included
MCU-S1NEK1N
Up to 8 units
Up to 8 units
16 kW
32.0 kW
16 kW
16 kW