Download Print this page

Danfoss VFS 2 Datasheet

Seated valve for steam pn25, 2-way valve, flange

Advertisement

Quick Links

Data sheet
Seated valve for steam (PN 25)
VFS 2 – 2-way valve, flange
Description
Ordering
Example:
2-way valve, DN 15, k
1.6, PN 25,
VS
t
200 °C, flange connection
max
-
1× VFS 2 DN 15 valve
Code No.: 065B1513
© Danfoss | 2016.11
VFS 2 valve is a range of 2 port flanged valve
for chilled water, LPHW, MPHW, HPHW (low,
medium or high pressure hot water) and steam
applications.
2-way valve VFS 2
kVS
DN
PN
(m3/h)
0.4
0.63
1.0
15
1.6
2.5
4.0
20
6.3
25
25
10
32
16
40
25
50
40
65
63
80
100
100
145
The valve is designed to be combined with
following actuators:
• DN 15-50
• DN 65-100 AMV(E) 55, AMV(E) 56, AMV(E) 85,
Features:
• Logarithmic characteristic
• Control range 30:1 / 50:1 / 100:1
• Suitable for steam applications
Main data:
• DN 15-100
• k
• PN 25
• Medium:
Circulation water/glycolic water up to 50 % /
steam (max. Δp = 6 bar)
• Temperature:
1)
• Logarithmic characteristic
• Flange PN 25 connections
• Compliance with Pressure Equipment
Directive 2014/68/EU.
Spare parts – stuffing box
tmax.
Code No.
(oC)
065B1510
065B1511
065B1512
065B1513
065B1514
065B1515
065B1520
200
065B1525
065B1532
Accessories
065B1540
Type
065B1550
Stem heater 24 V AC/DC
065B3365
(AMV(E) 25, 35 and VFS 2 valves DN 15-50)
065B3380
Stem heater 24 V AC/DC
(AMV(E) 56 and VFS 2 valves DN 15-50)
065B3400
Stem heater 24 V AC/DC
(AMV(E) 85, 86 and and VFS 2 valves DN
65-100)
Stem heater 24 V AC/DC
(AMV(E) 55, 56, 655, 658, 659 and VFS 2
valves DN 65-100)
Adapter AMV(E) 25 (SU/SD), AMV(E) 35
and VFS 2 DN 15-50
(for media temperatures over 150 °C)
Clutch
(AMV(E) 56 and VFS 2 valves DN 15-50)
AMV(E) 25 (SU/SD), AMV(E) 35,
AMV(E) 56 (with clutch 065Z7551)
AMV(E) 86, AMV (E) 65x
0.4-145 m
/h
3
VS
2 (–10
) ... 200 °C
1)
At temperatures from -10 °C up to +2 °C use stem heater
DN
Description
15
20
Four PTFE rings
Seal for valve cover
25
Gland ring
32
Washer
Instructions
40
50
65
Three PFTE rings
80
Gland ring
Instructions
100
Code No.
065B0001
065B0006
Code No.
065B2171
065Z7020
065Z7021
065Z7022
065Z7548
065Z7551
VD.HC.L3.02 | 1

Advertisement

loading

Summary of Contents for Danfoss VFS 2

  • Page 1 2 (–10 ) … 200 °C At temperatures from -10 °C up to +2 °C use stem heater VFS 2 valve is a range of 2 port flanged valve • Logarithmic characteristic for chilled water, LPHW, MPHW, HPHW (low, • Flange PN 25 connections medium or high pressure hot water) and steam •...
  • Page 2 If max. closing pressure is smaller than 4 bar than the recommended Δp is the same as closing Δp. Values in parentheses [ ] are based on the force of the actuator AMV(E) 25 SU/SD only. © Danfoss | 2016.11 2 | VD.HC.L3.02...
  • Page 3: Installation

    AMV(E) 25(SU/SD)/35 AMV(E) 55/56 AMV(E) 65x AMV(E) 85/86 = 150°C ... 200°C AMV(E) 25 (SU/SD), 35 Adapter for VFS 2 DN 15-50 ≈5 ≈5 Hydraulic connections Leave sufficient clearance to facilitate the Mount according to flow direction as indicated dismantling of the actuator from the valve body for maintenance purposes.
  • Page 4 16 gives a valve pressure drop of 12.7 kPa valves. In this case, a valve with k 6.3 would give (point H). a pressure drop of 90.7 kPa (point C): © Danfoss | 2016.11 4 | VD.HC.L3.02...
  • Page 5 At this condition the steam stroke will merely increase the velocity of the is travelling at or close to its critical velocity steam without reducing the volumetric flow. © Danfoss | 2016.11 VD.HC.L3.02 | 5...
  • Page 6 The maximum flow for same inlet pressure recommended ratio of 40%). is found by extending the vertical line (C-E) through point E until it crosses the k 25 line F-F (point E’’’) and reading off the flow (1700 kg/h). © Danfoss | 2016.11 6 | VD.HC.L3.02...
  • Page 7 Data sheet VFS 2 Dimensions min. 150 min. 100 adapter VFS 2 (DN 15-50) + VFS 2 (DN 15-50) + 065Z7548 AMV(E) 25, 35 (SU/SD) AMV(E) 56 + clutch 065Z7551 Valve weight (number) (kg) 11.7 min. 118 min. 81 min. 150...
  • Page 8 VFS 2 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed.