VX Solo II
Instructions for installation and use
Danfoss District Energy

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss VX Solo II Series

  • Page 1 MAKING MODERN LIVING POSSIBLE VX Solo II Instructions for installation and use Danfoss District Energy...
  • Page 2: Table Of Contents

    15.1 Maintenance schedule (recommendations) ................................. 34 16.0 Troubleshooting ............................................... 35 16.1 Troubleshooting - Heating ........................................35 16.2 Troubleshooting - Domestic hot water ................................... 37 17.0 EU Declaration of Conformity ........................................39 18.0 Commissioning Certificate ........................................... 41 DKDHR VI.GP.P2.02 Danfoss District Energy...
  • Page 3: Product Introduction

    Please note that the ball valves are supplied loose with the substation, - for mounting on site. Accessories available as extra equipment (mounting on site) RAVK 25-65/VMA thermostatic valve for DHW - Code No. 144B2021 Primary Secondary Danfoss District Energy VI.GP.P2.02 DKDHR...
  • Page 4: Vx Solo Ii H (Ecl 210/A230) - 1 He Circuit

    24 Fitting piece for heat meter VX Solo II H (ECL 210/A230) - 1 HE circuit 5 Strainer ¾” x 110 mm 7 Ball valve 25 Controller Danfoss ECL210/ 8 Circulation pump HE A230 11 Safety valve HE 26 Outdoor sensor , ESMT...
  • Page 5: Vx Solo Ii H2 (Ecl 210/A260) - 2 He Circuits

    Plate heat exchanger, HE, with insulation Sensor Danfoss, ESMC Strainer Danfoss actuator AMV 13, HE Non-return valve Danfoss flow controller with integrated control valve AHQM Ball valve Danfoss actuator AMV 150, FH Supply limit Circulation pump HE 3-way valve VMV...
  • Page 6: Vx Solo Ii Hwp (Ecl 210/A237) - 1 He Circuit + Prim. Connection For Dhw Cylinder

    23 Sensor pocket for heat 7 Ball valve Storage cylinder meter 8 Circulation pump HE 24 Fitting piece for heat meter 11 Safety valve HE 25 Controller Danfoss ECL 13 Thermometer Comfort 210/A237 Cylinder 26 Outdoor sensor, ESMT supply 27 Sensor, ESMC...
  • Page 7: Vx Solo Ii Hwp (Ecl 210/A247) - 1 He Circuit + Prim. Connection For Dhw Cylinder

    23 Sensor pocket for heat with insulation meter 5 Strainer 24 Fitting piece for heat meter Supply limit 7 Ball valve 25 Controller Danfoss ECL 8 Circulation pump HE Comfort 210/A247 Storage cylinder 11 Safety valve HE 26 Outdoor sensor, ESMT 13 Thermometer...
  • Page 8: Vx Solo Ii H2Wp (Ecl 210/A260) - 2 He Circuits + Prim. Connection For Dhw Cylinder

    7 Ball valve 24 Fitting piece for heat meter 33 Actuator AMV 150, FH 4 Differential pressure controller 8 Circulation pump HE 25 Controller Danfoss ECL 34 Three way valve VMV with flow limitation AVPB-F 10 Circulation pump FH Comfort 210/A260...
  • Page 9: Vx Solo Ii H2Wp (Ecl 310/A377) - 2 He Circuits + Prim. Connection For Dhw Cylinder

    10 Circulation pump FH 24 Fitting piece for heat meter control valve AHQM 57 Safety thermostat, HE circuit 11 Safety valve FH 25 Controller Danfoss ECL 31 Actuator AMV 150, Cylinder Comfort 310/377 32 Flow controller with integrated Supply limit...
  • Page 10: Vx Solo Ii Hws (Ecl 210/A237) - 1 He Circuit + Sec. Connection For Dhw Cylinder

    VX Solo II HWS (ECL 210/A237) - 1 HE circuit + sec. connection for DHW cylinder 1 Plate heat exchanger HE 24 Fitting piece for heat meter 5 Strainer 25 Controller Danfoss ECL 6 Non-return valve Comfort 210/A237 Supply limit...
  • Page 11: Vx Solo Ii Hws (Ecl 210/A247) - 1 He Circuit + Mixing Loop, Sec. Connection For Dhw Cylinder

    Radiator heating / Supply 15 Manometer Floor heating 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 25 Controller Danfoss ECL Return Comfort 210/A247 26 Outdoor sensor ESMT 27 Sensor, ESMC Cylinder Supply Supply...
  • Page 12: Vx Solo Ii H2Ws (Ecl 210/A267) - 2 He Circuits + Sec. Connection For Dhw Cylinder

    57 Safety thermostat, HE circuit return 16 Expansion vessel 23 Sensor pocket for heat meter FH supply 24 Fitting piece for heat meter 25 Controller Danfoss ECL Comfort 210/A267 26 Outdoor sensor ESMT 27 Sensor, ESMC FH return Supply Supply...
  • Page 13: Dimensional Sketch / Connections

    District heating (DH) supply District heating (DH) return Heating (HE) return Heating (HE) supply Floor heating supply Floor heating return Cylinder supply Cylinder return Wall Connections size: G¾” (ET) DCW, DHW, HE: G¾” (IT top view 13 13 Danfoss District Energy VI.GP.P2.02 DKDHR...
  • Page 14: Enduser Instructions, General

    For wall-mounting and with variable connection possibilities. The HE supply temperature is controlled either by a self-acting ther- mostat T°C 200 or by a Danfoss ECL controller in combination with an electronic actuator. The ECL controller acts as the brain of the heating system.
  • Page 15: Enduser Instructions, Adjustment And Setting

    Electronic control The temperature for the heating circuit can be controlled electroni- cally by either a Danfoss ECL 210 or a Danfoss ECL 310 controller (Fig. 3). The supply temperature ist calculated by the controller on basis of the outdoor temperature.
  • Page 16: Installation Instructions, Safety And Handling

    The substation is made of materials that cannot be disposed of together with household waste. Close all energy sources and disconnect all connection pipes. Disconnect and dismantle the product for disposal in accordance with the applicable local regulations for the disposal of the individual components. 16 DKDHR VI.GP.P2.02 Danfoss District Energy...
  • Page 17: Installation Instructions - Getting Started

    41. IMPORTANT! Heating and cooling the substation may cause leaks. Therefore it may be necessary to retighten the connec- tions in the period after commissioning. 17 17 Danfoss District Energy VI.GP.P2.02 DKDHR...
  • Page 18: Description Of Vx Solo Variants

    In rooms with radiators, the temperature is regulated using the radiator thermostats. Alternatively, the heating circuits can be regulated using fully auto- matic Danfoss ECL weather compensation equipment, - a Danfoss VX Solo II H2 (ECL 210/A260) VX Solo II HWP (ECL 210/A237)) ECL controller in combination with electronic actuator(s).
  • Page 19: Installation Instructions, General

    Always lead the blow-off pipes from the safety valves to a drain in accordance with applicable legislation. Expansion vessel The VX Solo II substations are equipped with an expansion vessel, which is factory set to 0,5 bar. 19 19 Danfoss District Energy VI.GP.P2.02 DKDHR...
  • Page 20 Mount the return flow sensor in the heat meter housing (pos. C) or in the sensor pocket on DH return (pos. B). Pipe bushing ½”/M10x1 incl. plug M10 Please note: Some variants are supplied with ½” plug. 20 DKDHR VI.GP.P2.02 Danfoss District Energy...
  • Page 21 230 V a.c. - 50 Hz Power consumption 2 / 7 VA For VX Solo II substations supplied with Danfoss ECL electronic For further information please refer to the enclosed instructions. controller the control equipment includes actuator(s) and sensors installed in the unit and the controller. The controller is electrically Pumps (Alpha2 L &...
  • Page 22: Adjustment And Commissioning, Filling The System And Differential Pressure Controller

    1 kPa (0.01 bar). The controller settings can be changed in accordance with the en- closed producer instructions: AVPL Differential pressure controller (PN 16) AVPL Return mounting, adjustable setting VI.CB.T1.6K © Danfoss 05/03 7369316-0 SIBC 22 DKDHR VI.GP.P2.02 Danfoss District Energy...
  • Page 23 The controller is equipped with excess pressure safety valve, which protects the actuator from too high differential pressure. Please see enclosed instructions, AVPB-F Flow setting Flow setting is being done by the adjust- ment of the flow restrictor position. 23 23 Danfoss District Energy VI.GP.P2.02 DKDHR...
  • Page 24: Adjustment And Commissioning, Heating Circuit

    24 V Class II transformer (SELV) 230 V max. 3 A pre-fuse VI.SB.H3.02 12-2005 Produced by Danfoss Industri Service 05.09 JJ-Bi.DS for further information. It is recommended to avoid fully opened thermostats on some radiators and fully shut-off on others. Higher temperature at the top and lower temperature at the bottom part of radiators means that the system operation is correct.
  • Page 25 Danfoss ECL Comfort 210 or 310 The temperature for the heating circuits can be controlled electroni- cally by a Danfoss ECL 210 or 310 controller. The ECL controller is supplied with an ECL Application Key , which contains information about application, language and factory settings, adapted to the type of system, for which it is ordered.
  • Page 26 VX Solo II substations AHQM / AMV 150 The VX Solo II substations can be supplied with a self-acting flow controller with integrated control valve Danfoss AHQM and an elec- trical actuator AMV 150 The controller closes when set max. flow is exceeded.
  • Page 27 РУССКИЙ Электроприводы для трехпозиционного регулирования AMV 150 www.danfoss.ru Страница 7 (mm) (mm) (mm) EI.97.Q2.00 © Danfoss 12/01 7369267-9 SIBC R&D 73691180 DH-SMT/SI VI.KU.N2.1J © Danfoss 01/2008 VS 2 Press and hold the button (on the bottom side of the actuator) during manual override.
  • Page 28 From factory the Jumo AT safety thermostat is pre-wired to the Danfoss ECL controller with a 2 m cable, enabling the thermostat housing to be mounted in any mounting position on the house- hold piping (HE supply) on site.
  • Page 29 ALPHA2 L, Installation and operating instructions Summer operation Substations with Danfoss T°C Thermostat In the summer, you can stop the pump by switching it off at the mains. However, remember to start the pump (briefly) at least once a month during the summer.
  • Page 30: Circulation Pump, Heating Circuit

    For start-up follow the above start-up instructions. It is recommend- able to vent the system after the summer period again. Substation with Danfoss ECL: The circulation pump for heating is automatically switched off in periods without heat demand. To prevent the pump from block- ing in periods without heat demand, the controller automatically switcheson the pump for some minutes every third day.
  • Page 31: Adjustment And Commissioning, Dhw Cylinder Circuit

    The temperature in the DHW cylinder can be controlled by the Danfoss ECL controller in combination with an actuator + valve. Danfoss ECL Comfort 210/310 The application Key contains information about application, language and factory settings, adapted to the type of system, for which it is ordered.
  • Page 32: Pump, Dhw Cylinder Circuit

    (ELC 210/A247) and the VX Solo II H2WP (ECL 310/A377) are sup- Manual override (AMV 150) plied with electrical actuator type Danfoss AMV 150 with Danfoss valve housing type AHQM placed on the primary return flow pipe. The AMV actuator is electrically wired to the controller from the plant.
  • Page 33: Maintenance

    If rinsing with clean water is not sufficient, the exchanger can also be cleaned by circulating a cleaning agent approved by Danfoss (e.g. Kaloxi or Radiner Fl cleaning fluid) through the exchanger. Both these cleaning fluids are environmentally friendly and can be disposed off through the standard sewer system.
  • Page 34: Maintenance Schedule (Recommendations)

    Please note that the connections may feature EPDM gaskets! Therefore, it is important that you DO NOT OVERTIGHTEN the pipe connections. Over-tightening may result in leaks. Leaks caused by over-tightening or failure to retighten connections are not covered by the warranty. 34 DKDHR VI.GP.P2.02 Danfoss District Energy...
  • Page 35: Troubleshooting

    Defective sensor. Replace sensor. Supply temperature too high Call in automatic controls manufacturer Defective controller. The controller does or replace controller. not react as it is should in accordance with the instructions. 35 35 Danfoss District Energy VI.GP.P2.02 DKDHR...
  • Page 36 The system is single-pipe. It is extremely important to keep the supply temperature to the radiators as low as ever possible, while maintaining a reasonable level of comfort. 36 DKDHR VI.GP.P2.02 Danfoss District Energy...
  • Page 37: Troubleshooting - Domestic Hot Water

    Defective immersion sensor. Replace immersion sensor. Non-return valve on the circulation line Replace non-return valve. defective (leads to mixing - and the circulation water pipes become cold dur- Variations in temperature ing tapping). 37 37 Danfoss District Energy VI.GP.P2.02 DKDHR...
  • Page 38 Immersion sensor placed incorrectly. Place immersion sensor correctly in ac- cordance with the manufacturer instruc- tions for the cylinder. You may contact Danfoss Redan A/S for further information. Calified heating element. Clean DHW cylinder with acid solution or replace heating element.
  • Page 39: Eu Declaration Of Conformity

    Telephone +45 87 43 89 43 EC-DECLARATION OF CONFORMITY For CE marking in EU (European Union) Danfoss Redan A/S District Energy DK-8382 Hinnerup Declares under our sole responsibility that below products including all available power and control options: VX Solo II Main components: See instruction manual.
  • Page 40 Instructions for installation and use VX Solo II substations 40 DKDHR VI.GP.P2.02 Danfoss District Energy...
  • Page 41: Commissioning Certificate

    Over-tightening may result in leaks. Leaks caused by ove-rtightening or failure to retighten connections are not covered by the warranty. To be filled-out by the installer. This substation has been retightened, adjusted and commissioned on the: by installer: Date/Year Company name (stamp) 41 41 Danfoss District Energy VI.GP.P2.02 DKDHR...
  • Page 42 Instructions for installation and use VX Solo II substations 42 DKDHR VI.GP.P2.02 Danfoss District Energy...
  • Page 43 Instructions for installation and use VX Solo II substations 43 43 Danfoss District Energy VI.GP.P2.02 DKDHR...