Setting The Outdoor Unit Eeprom Data - Panasonic U-8ME1E81 Service Manual

2way vrf system
Hide thumbs Also See for U-8ME1E81:
Table of Contents

Advertisement

1. Outdoor Unit Maintenance Remote Controller
1. Outdoor Unit Maintenance Remote Controller

1-6. Setting the outdoor unit EEPROM data

This function is used to make the outdoor unit EEPROM
data settings.
Setting mode 1
Press and hold the
(VENTILATION) button simultaneously for
4 seconds or longer.
Press the temperature setting
buttons to change the item code. The item codes
and setting data are shown in the table of
"List of Item Codes" on the next page.
Press the timer time
change the setting data.
To confirm the changed setting data, press the
(SET) button.
(At this time, the "
blinking and remains lit.)
During this mode, "
blinking. The outdoor unit address display section
displays "
," the item code and number (DN
value in the table), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The
display changes between the first 3 digits (Fig. (A))
and the last 3 digits (Fig. (B)).
When the first 3 digits are displayed, the bottom dot
of the colon is illuminated.)
To exit setting mode, press the
button.
DN
Parameter
Snowfall sensor usage
Outdoor unit fan Quiet
mode
Energy saving mode
Energy saving operation
plug
Demand 1 current
Demand 2 current
High static pressure mode
(CHECK) button and the
and
and
buttons to
" display stops
" is displayed,
(CHECK)
000 = Sensor input not present. Control is performed.
001 = Sensor input present. Control is performed.
002 = Sensor input not present. Control is not performed.
003 = Sensor input present. Control is not performed.
000 = Disabled
002 = Quiet mode 2
004 = Quiet mode 4 ...
000 = None
001 = Discharge temp. control only (Mode 3)
002 = Demand only (Mode 2)
003 = Discharge temp. control + Demand (Mode 1)
000 = Independent
001 = All indoor units linked
000 = 0%
130 = 130% ...
000 = 0%
130 = 130% ...
000 = Disabled
* Charge when the external static pressure is increased to over 30 Pa.
(A) Display of first 3 digits
5
1
(B) Display of last 3 digits
5
1
(A) and (B) are displayed alternately.
(Example shows display of 000 001.)
Description
001 = Quiet mode 1
003 = Quiet mode 3
012 = Quiet mode 12
040 = 40% ...
070 = 70% ...
-001 = no limit
040 = 40% ...
070 = 70% ...
-001 = no limit
001 = High static pressure mode
6-9
2WAY SYSTEM
2WAY SYSTEM
Service Checker
Service Checker
3
3
100 = 100% ...
100 = 100% ...
2
1
2
2
3
4
5
6
7
8