Troubleshooting
4-3-24 Low Pressure sensor error (Open/Short)
Outdoor unit
display
Duct, Cassette (1/2 Way),Console, Celing
Operation Defrost
Indoorunit
×
display
※ ●: ON ◑: Flash ×: OFF
Judgment
∙ Refer to the judgment method below.
Method
Cause of
∙ Disconnection or breakdown of relevant sensor.
problem
1. Low Pressure sensor Open/Short error determination method
1) Identifies from when power is supplied or 2 minutes after RESET, and only when set is stopped.
2) An Open/Short error will occur if the input voltage standard range of 0.5V ~ 4.95V is exceeded.
2. Inspection Method
Low pressure
sensor connector (CN41)
connected to PCB?
Is there refrigerant inside the set?
(Please check by connecting the Manifold gauge
to the service valve)
Low pressure sensor terminal of PCB : Is the
voltage between 3 and 4 pins 5V?
Replace Low Pressure sensor
4-46
Timer
Fan Filter/MPI Operation Defrost
×
◑
◑
◑
Yes
Yes
Yes
Cassette (4/Mini4 Way)
Timer
Filter Operation
×
◑
◑
No
Please re-inspect after connecting
No
No
The ▼ mark is the 1st pin on the PCB.
Wall-mounted (NeoForte)
Timer
Turbo
◑
●
◑
the connector to the PCB
Refill refrigerant after vacuum
Replace PCB