Internal Communication Error Of The Outdoor Unit C-Box - Samsung AM080xXV Series Service Manual

Outdoor unit
Table of Contents

Advertisement

Troubleshooting

4-3-6 Internal Communication error of the Outdoor Unit C-Box

Outdoor unit
display
Duct, Cassette (1/2 Way),Console, Celing
Operation Defrost
Indoorunit
×
display
※ ●: ON ◑: Flash ×: OFF
Judgment
∙ Communication error between the C-Box PCB
Method
∙ Communication wire inside the C-Box is unconnected
Cause of
problem
∙ Main PCB defective
1. Cause of problem
Is the jumper connector connected to CN31 of
Inverter PCB2(when the Comp. applied one :
Inverter PCB1)?
Is Inverter PCB1 CN32 and Inverter PCB2
CN31 connector accurately connected?
PCB1 CN32 and Fan PCB CN12 connector
accurately connected?
Does FAN PCB LD22/LD32 (LED) blink?
Replace Main PCB
4-26
- All boards of outdoor unit are not communicating
Timer
Fan Filter/MPI Operation Defrost
×
Yes
Yes
Is Inverter
Yes
Yes
Cassette (4/Mini4 Way)
×
×
No
Two Comp. applied to the model
No
No
No
Wall-mounted (NeoForte)
Timer
Filter Operation
×
×
Restart operation after connecting the Inverter
PCB2 CN31(when the Comp. applied one :
Inverter PCB1) connector. (Check the 3, 4 Pin short)
* Service after turn off the Main Power.
Restart operation after checking the Inverter
PCB2 CN31 and PCB2 CN32 Communication
wire/Connector.(3, 4 Pin Short)
* Service after turn off the Main Power.
1) Check the Inverter PCB1 CN32, CN91 and
Fan PCB CN12 Communication wire/
Connector.
2) Restart operation after connecting the Hub
PCB CN97 and Fan PCB CN13 connector.
* Service after turn off the Main Power.
1) Check the Main PCB : Main PCB TX circuit
inspection
2) Check the Hub PCB : Hub PCB TX circuit
inspection
* Service after turn off the Main Power.