No.
Part name
1) Perform work of item 1 of
Compressor
2) Extract refrigerant gas.
3) Remove the partition plate.
4) Remove the sound-insulation material.
5) Remove terminal cover of the compressor,
Never reuse the compressor lead which you
disconnected. Use the new one. If you reuse
it, it may malfunction.
6) Remove pipe connected to the compressor
7) Remove the fixing screw of the bottom plate
8) Remove the fixing screw of the bottom plate
9) Pull upward the refrigeration cycle.
10)
1) Perform work of item 1 of
Reactor
2) Remove screws fixing the reactors.
Procedure
.
and
,
,
,
(ST2TØ4 × 10L 4 pcs.)
and disconnect lead wire of the compressor
from the terminal.
NOTE
with a burner.
• Take care to keep the 4-way valve away
from naked flames. (Otherwise, it may
malfunction.)
and heat exchanger. (ST2TØ4 × 10L 1 pc.)
and valve fixing plate.
(ST2TØ4 × 10L 2 pcs.)
Remove NUT (3 pcs.) fixing the
compres-sor to the bottom plate.
(ST2TØ4 × 10L 2 pcs.)
, and
.
- 80 -
FILE NO. SVM-18041
Remarks