Others; Refrigerant Recovery Control - Toshiba RAV-GP561ATP-E Service Manual

Air-conditioner (split type), outdoor unit
Hide thumbs Also See for RAV-GP561ATP-E:
Table of Contents

Advertisement

9-1. Calling of Check code History
<Contents>
The trouble contents in the past can be called.
<Procedure>
1
Push
+
buttons simultaneously for 4 seconds or
more to call the service check mode.
Service check goes on, the CODE No.
then the content of the latest alarm is displayed.
The number and trouble contents of the indoor unit in which a
trouble occurred are displayed.
2
In order to monitor another check code history, push
the set temperature
check code history No. (CODE No.).
01 01 01 01 01
CODE No.
(Latest)
NOTE : 4 check code histories are stored in memory.
3
Pushing
button returns the display to usual
display.
REQUIREMENT
Do not push
button, otherwise all the check code histories of
the indoor unit are deleted.
NOTE
The electric portion of the refrigerant recovery SW on the sub-board
is electrified, therefore be careful to an electric shock.

9. OTHERS

01
is displayed, and
/
buttons to change the
04 04 04 04 04
CODE No.
(Old)
- 64 -
FILE NO. SVM-18041
TEMP.
TIMER SET
TIME
FILTER
RESET
TEST
SET
CL
2
3 1
<Operation procedure>
1
2
3
Returned to usual display
ON / OFF
FAN
MODE
SAVE
VENT
SWING/FIX
UNIT LOUVER