Carrier AquaEdge 19XR Start-Up, Operation And Maintenance Instructions Manual page 21

Two-stage semi-hermetic centrifugal liquid chillers with pic 5 controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

Fig. 16 — Lock Icon
The User Login Screen is displayed. Enter the password on this
screen. See Fig 17. The language and system of measurement can
also be changed on this screen. For details, see the 19XR with PIC
5 Controls Operation and Troubleshooting guide.
INPUT TIME AND DATE
Set day and time and if applicable Holidays through MAIN
MENU  CONFIGURATION MENU  DATE/TIME
CONFIGURATION. See the Controls Operation and Trouble-
shooting guide for details. Because a schedule is integral to the
chiller control sequence, the chiller will not start until the time
and date have been set.
NOTE: The date format is MM-DD-YY for English units and
DD-MM-YY for SI units.
PARAMETER
Starter Type
Motor Rated Line Voltage
Volt Transformer Ratio
Motor Rated Load Amps
Motor Locked Rotor Trip
Starter LRA Rating
Motor Current CT Ratio
Current % Imbalance
Ground Fault Current Transformers
Ground Fault CT Ratio
Single Cycle Dropout
Line Frequency
Line Frequency Faulting
Hot Gas Bypass Option
Minimum Load Points (Tsmin, IGVmin)
Full (Maximum) Load Points (Tsmax, IGVmax)
Surge Line Shape Factor (shapefac)
Chilled Medium
Evaporator Refrigerant Trippoint
Evaporator Flow Delta P Cutout
Condenser Flow Delta P Cutout
High Condenser Water Delta P
Motor Rated Kilowatts
*With variable flow systems this point may be configured to the lower end of the
range.
NOTE: Other parameters: Screens are normally left at the default settings; they may
be changed as required. The time and persistence settings on the CONF_ISM table
can be adjusted to increase or decrease the sensitivity to a fault condition. Increas-
ing time or persistence decreases sensitivity. Decreasing time or persistence
increases sensitivity to the fault condition.
Table 7 — Job Site Parameters
CONF_ISM — Select 0 for full voltage, 1 for reduced voltage, 2 for solid state, or 3 for free-standing variable
frequency drive.
CONF_ISM — Motor rated voltage from chiller information nameplate.
CONF_ISM — Enter ratio (reduced to a ratio to 1) of power transformer wired to terminal J3 of ISM. If no transformer is
used enter 1.
CONF_ISM — Per chiller nameplate data. RL AMPS on compressor nameplate.
CONF_ISM — Per chiller identification nameplate.
CONF_ISM — Enter value from nameplate in starter cabinet MAXIMUM FUSE. This value shall always be "9999" for
Benshaw RediStart MX3 wye-delta and solid-state starters.
CONF_ISM — Enter ratio (reduced to a ratio to 1) of current transformers wired to terminal J4 of ISM. This value shall
always be "100" for Benshaw RediStart MX3 and solid-state starters.
CONF_ISM — Current imbalance trip threshold. Enter up to 100% for starter type 3 (VFD).
CONF_ISM — Enter 0 if no ground fault CTs are wired to terminal J5 of ISM. Enter 1 if ground fault CTs are used.
CONF_ISM — Enter ratio (reduced to a ratio to 1) of ground fault CT.
CONF_ISM — ENABLE if motor protection required from drop in line voltage within one cycle.
CONF_ISM — Enter YES for 60 Hz or NO for 50 Hz.
CONF_ISM — ENABLE if motor protection required for drop in line frequency.
CONF_OPT — 1 = HGBP for Surge Correction; 2 = HGBP for Low Load Operation; 3 = Combination HGBP; 0 = no
HGBP or HGBP is Disabled.
CFGSURGE — Per job data — See modify load points section. Refer to table located in the control panel.
CFGSURGE — Chiller Requisition (TSmin, IGV min) or per job data — See modify load points section. Refer to table
located in the control panel.
CFGSURGE — Per Chiller Requisition (shapefac). Refer to table located in the control panel.
FACTORY — Enter water or brine.
CFGLIMIT — Usually 3°F (1.7°C) below design refrigerant temperature.
CFGLIMIT — Per Chiller Requisition if available or enter 50% of design pressure drop to 0.5 psi (3.4 kPa).*
CFGLIMIT — Per Chiller Requisition if available or enter 50% of design pressure drop to 0.5 psi (3.4 kPa).*
CFGLIMIT — Enter the maximum allowable value for condenser water pressure drop.
FACTORY — Enter value from chiller requisition form (product data submittal) if DEMAND LIMIT SOURCE is set to kW.
21
User Login Screen
Fig. 17 — User Login Screen
MODIFY CONTROLLER IDENTIFICATION IF NECESSARY
The module address can be changed from the Configuration
Menu. Change this address under CONTROL IDENTIFICA-
TION for each chiller if there is more than one chiller at the
jobsite. Write the new address on the HMI module for future
reference.
CONFIGURE SERVICE TABLES
Access the SERVICE tables through MAIN MENU CON-
FIGURATION MENU to modify or view the job site parame-
ters shown in Table . For details, see the 19XR with PIC 5 Con-
trols Operation and Troubleshooting guide.
TABLE