19XR PIC 5 CFGSURGE SURGE CORRECTION CONFIG TABLE CONFIGURATION SHEET
DESCRIPTION
Surge Line Configuration
0 = PR
1 = Delta T
IGV1 Pos Configuration
0 = Degree
1 = Percentage
Surge Delta Tsmax
Surge Delta Tsmin
PR at Full Load Opening
PR at Min Load Opening
IGV1 Full Load Open Deg
Sound Ctrl IGV1 Open Deg
IGV1 Minimum Open Deg
IGV1 Maximum Open Deg
IGV1 Minimum Position
IGV1 Full Load Position
Envelop Line Offset
Envelop Lower Deadband
Envelop Upper Deadband
Surge Line Shape Factor
Sound Line Shape Factor
Envelop Speed Factor
Surge Delay Time
Surge Time Period
Surge Delta Amps %
GV1 Close Step Surge
VFD Speed Step Surge
EC Valve Step Surge
Surge Profile Offset
High Efficiency Mode
High Noise Alert
19XR PIC 5 CTRL_ID CONTROL IDENTIFICATION TABLE CONFIGURATION SHEET
DESCRIPTION
CCN Element Number
CCN Bus Number
CCN Baud Rate
Device Description — 19XRPIC5
Location Description (User-defined
24-digit character string)
Software Part Number:
SCG-SR-2-M200300330
Serial Number = 1
RANGE
0 to 1
0 to 1
0 to 150
0 to 150
1 to 5
1 to 5
80 to 120
degrees
10 to 40
degrees
0 to 10
degrees
90 to 120
degrees
0 to 100
0 to 100
1 to 3
0.5 to 3
0.1 to 3
–1 to 0
0 to 1
0 to 2
0 to 120
7 to 10
5 to 40
1 to 3
1 to 5
1.0 to 10.0
0.0 to 5.0
DSABLE/ENABLE
DSABLE/ENABLE
RANGE
0 to 239
0 to 239
9600, 19200, 38400
CL-10
UNITS
DEFAULT
0
0
^F
70
^F
45
3.0
1.5
88
27
2
109
%
5
%
100
^F
2
^F
1.5
^F
1.5
–0.010
0.010
2.0
sec
15
min
8
%
20
%
2
%
3
%
4.0
^F
0.0
ENABLE
DSABLE
UNITS
DEFAULT
1
0
9600
VALUE
VALUE