036-21423-001 Rev. A (0602)

Sensor Connections

PRESSURE
SENSOR
TB12
ANALOG
INPUTS
+V
+V
1
2
3
4
5
6
7
8
G
G
To Bypass
Actuator Feedback

Figure 7: Existing EZ Zone Master Controller Sensor Wiring

Splice As
Required
Static
Pressure
Sensor
LO
HI
PJ1
ANALOG
R7
INPUTS
D2
R8
+12V
D3
D4
SAT
D5
R9
RAT
D6
R10
D8
OAT
AUX1
AUX2
AUX3
GND
GND
TB3
EXHAUST
CONTACTS
N.O.
TB4
ANALOG
OUTPUTS
A1
A2
G
TB5

Figure 8: New Meridian Zone Manager Sensor Wiring

Upgrade
Splice As
Required
Static
Pressure
Sensor
LO
HI
Static
Pick-up
Supply Air
Sensor
Static
Pick-up
Supply Air Temp.
Sensor
Return Air Temp.
Sensor
Outdoor Air Temp.
Sensor
EZ Zone/Meridian
The EZ Zone Master Controller sensor connec-
tions are located on the right side of the board.
Only a supply air temperature sensor and the
bypass actuator feedback are connected here.
The Meridian Zone Manager includes terminals
for connecting the following sensors:
Supply Air Temperature
Return Air Temperature
Outside Air Temperature
The terminals are marked SAT, RAT, and OAT
for ease of wiring. Auxiliary input terminals
AUX1, AUX2 and AUX3 are used for Econo-
mizer Disable, Dirty Filter Alarm and Forced
Occupied Mode. Bypass damper feedback has
been relocated (see next page).