Cabinet Placement

Service clearances should be maintained that are similar to the following.
Front access: 91.5 cm (36 inches)
Back (rear) access: 76.2 cm (30 inches)
If you are installing the cabinet on a raised floor (with data and power cables
underneath), the back of the cabinet (cable entry area) should be positioned over the
floor tile cutout supplied to route power cords and data cables. See
.
FIGURE 2-2
Cabinet Placement Clearances
FIGURE 2-2
Note – The distance between the back of the cabinet and the customer's power
source connectors should be 2.4 meters (8 feet) or less.
Regulatory agencies require the control of emissions, and this is especially important
when the Sun StorageTek 6540 storage system is in place.
Caution – A front and rear door are required to be installed, and closed, when the
equipment is not being serviced. The rear door must remain physically attached and
closed (unless being serviced).
Follow basic procedures outlined in the appropriate installation manuals for
removing devices. Extender legs or tip-prevention (outrigger) legs are required to
enable personnel to slide out and remove or reinstall equipment as well as service
equipment and to perform maintenance.
12
Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide • July 2006