Setting PID Constants Manually
You set the PID constants manually in the Adjustment Level.
The default settings of the PID constants are as follows: P (proportional band) = 8.0°C, I (integral
time) = 233 seconds, D (derivative time) = 40 seconds.
1
Turn ON the power supply.
Operating Display
Press the
(Level) Key for less
than 1 second.
2
Change the parameter with the
Press the
several times to display p (P).
3
Change the parameter with the
Press the
Key several times to
display i (I).
4
Change the parameter with the
Press the
Key several times to
display d (D).
(When finished, press the
operation display.)
Simplicity on the Worksite
Adjustment Level
Key .
Adjustment Level
(Mode) Key
Key .
Adjustment Level
(Mode)
Key .
Adjustment Level
(Mode)
(Level) Key to return to the
Solutions Guide for FAQs: E5CC/E5EC
Using PID Control
←l.adj (L.ADJ) will be displayed
to show that the Adjustment
Level has been entered.
The four numeric digits that
identify the product code are
displayed.
←p (P): Indicates the Proportional
Band parameter.
←Default setting is 8.0 (8.0°C).
Change the set value with the
(Up
and Down) Keys.
←i (I): Indicates the Integral Time parameter.
←Default setting is 223 (233 seconds).
Change the set value with the
(Up
and Down) Keys.
←d (D): Indicates the Derivative Time parameter
←Default setting is 40 (40 seconds).
Change the set value with the
(Up
and Down) Keys.