Wiring Connection; Rs485 Communication Wiring; Rs232 Communication Wiring - Taie FY100 Communications Manual

Digital pid controller
Hide thumbs Also See for FY100:
Table of Contents

Advertisement

3.1 RS485 Communication Wiring

RS485 Converter
DCE
(T+)
(T-)
(R-)
TxON
(R+)
RxON
MODEL : IC485SN
RS485 Converter
DATA-
DATA+
MODEL : EDAM-8520
Note:
1. The length of shield wire should be less than 1200M.
2. Controllers in RS485 parallel connection should be less than 32 units

3.2 RS232 Communication Wiring

PC
3
TXD
RXD
2
GND
5
D sub connector (9 Pin)
Note:
1. The length of shield wire should be less than 12M.
2. There is only 1 unit of controller available in RS232 communication..
FY400/600/700/800/900 COMMUNICATION MANUAL

3 Wiring Connection

Shield Wire
1
2
3
4
Figure: 3.1-1
-
GND
DC24V
Vs+
+
Shield Wire
Figure: 3.1-2
Shield Wire
3 Wiring Connection
Controllers
DX -
DX +
DX -
DX +
Controllers
DX -
DX +
DX -
DX +
Controller
RD
SD
SG
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fy600Fy101Fy700Fy800Fy900Fy400

Table of Contents