Setting (Set Sv = 10.0 And Outl=100.0 To Slave Controller 1) - Taie FY100 Communications Manual

Digital pid controller
Hide thumbs Also See for FY100:
Table of Contents

Advertisement

Response from slave controller in abnormal status (Assumed as illegal data value)
Header
ID Number
(3AH)
(30H 31H)
(38H 36H)
1 is set to the MSB of function code in abnormal status (86H).
The abnormal code (03H) is returned as contents of error.
5.7.2

Setting (Set SV = 10.0 and OUTL=100.0 to slave controller 1)

Request message from master instrument:
Header
ID Number
Function
(3AH)
(30H 31H)
(31H 30H)
Data2
(30H 33H 45H 38H)
(39H 41H)
Response message from slave controller in normal status (When SV = 10.0 and
OUTL=100.0)
Header
ID Number
Function
(3AH)
(30H 31H)
(31H 30H)
Response from slave controller in abnormal status (Assumed as illegal register
address)
Header
ID Number
(3AH)
(30H 31H)
(39H 30H)
FY400/600/700/800/900 COMMUNICATION MANUAL
Function
Error Code
Code
(30H 33H)
Register Address
Code
(30H 30H 30H 30H)
LRC
Delimiter
(0DH 0AH)
Register Address
Code
(30H 30H 30H 30H)
Function
Error Code
Code
(30H 32H)
5 MODBUS ASCII Protocol
LRC
Delimiter
(37H 36H)
(0DH 0AH)
Data Count
(30H 30H 30H 32H)
Data Count
(30H 30H 30H 32H)
LRC
Delimiter
(0DH 0AH)
(36H 44H)
BYTE
Data1
Count
(30H 34H)
(30H 30H 36H 34H)
LRC
Delimiter
(45H 44H)
(0DH 0AH)
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fy600Fy101Fy700Fy800Fy900Fy400

Table of Contents