APPENDIX-A: REFERENCE DATA

This appendix provides reference for the following topics:

Wire selection guides

Battery size calculations
WIRE SELECTION GUIDES

Resistance of Solid Copper Wire

AWG
Ohms per Thousand Feet*
18
8.08
16
5.08
14
3.19
12
2.01
*NEC Chapter 9, Table 8.

Addressable Device Circuit Wire Selection Guide

Each addressable device circuit must meet the following requirements:
Total loop resistance - 50 ohm maximum with 50 devices
Total loop capacitance - 0.5uF max line to line per km and 1.0uF max line to shield per km
The terminal blocks of Siemens SLC devices are rated for a maximum of 14AWG wire.