TR200 MCB 105 Relay I/O Option Module
TR200 MCB 105 Relay I/O Option Module
The MCB 105 option includes 3 pieces of change over contacts and can be fitted into option slot B.
Electrical Data:
Max. terminal load (AC)
Max. terminal load (DC)
Min. terminal load (DC)
Max. switching rate at rated load/min. load
WARNING
Hazardous voltage with Dual Supply!
•
The label MUST be placed on the keypad frame as shown (UL approved).
•
The power to the frequency converter must be disconnected.
•
The power to the livepart connections on relay terminals must be disconnected.
Failure to follwo recommendations could result in death or serious injury.
•
Remove the keypad, the terminal cover and the cradle from the frequency converter.
•
Fit the MCB 105 option in slot B.
•
Connect the control cables and relieve the cables by the enclosed cable strips.
•
Various systems must not be mixed.
•
Fit the extended cradle and terminal cover.
•
Replace the keypad.
•
Connect power to the frequency converter.
•
Select the relay functions in par. 5-40 [6-8], par. 5-41 [6-8] and par. 5-42 [6-8].
Array [6] is relay 7, array [7] is relay 8 and array [8] is relay 9.
2
6 min -1 /20 sec -1
TR200 MCB 105 Relay I/O Option Module
240 V AC 2A
24 V DC 1A
5 V 10 mA