TR200 MCB 105 Relay I/O Option Module
TR200 MCB 105 Relay I/O Option Module
The MCB 105 option includes 3 pieces of change over contacts and can be fitted into option slot B.
Electrical Data:
Max. terminal load (AC)
Max. terminal load (DC)
Min. terminal load (DC)
Max. switching rate at rated load/min. load
WARNING
Hazardous voltage with Dual Supply!
The label MUST be placed on the keypad frame as shown (UL approved).
The power to the frequency converter must be disconnected.
The power to the livepart connections on relay terminals must be disconnected.
Failure to follwo recommendations could result in death or serious injury.
Remove the keypad, the terminal cover and the cradle from the frequency converter.
Fit the MCB 105 option in slot B.
Connect the control cables and relieve the cables by the enclosed cable strips.
Various systems must not be mixed.
Fit the extended cradle and terminal cover.
Replace the keypad.
Connect power to the frequency converter.
Select the relay functions in par. 5-40 [6-8], par. 5-41 [6-8] and par. 5-42 [6-8].
Array [6] is relay 7, array [7] is relay 8 and array [8] is relay 9.
2
6 min -1 /20 sec -1
TR200 MCB 105 Relay I/O Option Module
240 V AC 2A
24 V DC 1A
5 V 10 mA