Carrier 50HCQA05 Service And Maintenance Instructions page 10

Single package heat pump/electric heat nominal 3 to 10 tons with puron r-410a refrigerant
Hide thumbs Also See for 50HCQA05:
Table of Contents

Advertisement

Fig. 12 - - Cleaning Condenser Coil (Size 04- - 06 shown)
Fig. 13 - - Propping Up Top Panel
4. For Sizes 04- - 06: Remove screws securing coil to
compressor plate and compressor access panel.
5. For Sizes 07- - 12: Remove fastener holding coil sec-
tions together at return end of condenser coil. Care-
fully separate the outdoor coil section 3 to 4 in.
(7.6- - 10 cm) from the inner coil section. See Fig. 14.
6. Clean the outer surfaces with a stiff brush in the nor-
mal manner. Use a water hose or other suitable equip-
ment to flush down between the 2 coil sections to re-
move dirt and debris.
7. Secure inner and outer coil rows together with a
field- - supplied fastener.
8. Reposition the outer coil section and remove the coil
corner post from between the top panel and center
post. Reinstall the coil corner post and replace all
screws.
Totaline Environmentally Sound Coil Cleaner
Application Equipment:
S 2.5 gal (9.5L) garden sprayer
S Water rinse with low velocity spray nozzle
C08205
Fig. 14 - - Separating Coil Sections
UNIT DAMAGE HAZARD
Failure to follow this caution can result in corrosion
and damage to the unit.
Harsh chemicals, household bleach, acid or basic
cleaners should not be used to clean outdoor or indoor
coils of any kind. These cleaners can be very difficult
to rinse out of the coil and can accelerate corrosion at
C08206
the fin/tube interface where dissimilar materials are in
contact. If there is dirt below the surface of the coil,
use the Totaline Environmentally Sound Coil Cleaner
as described below.
UNIT DAMAGE HAZARD
Failure to follow this caution can result in reduced
unit performance.
High velocity water from a pressure washer, garden
hose, or compressed air should never be used to clean
a coil. The force of the water or air jet will bend the
fin edges and increase airside pressure drop.
Totaline Environmentally Sound Coil Cleaner
Application Instructions:
1. Proper protection equipment, such as approved safety
glasses and gloves, is recommended during mixing
and application of Totaline Environmentally Sound
Coil Cleaner.
2. Remove all surface loaded fibers and debris using a
vacuum cleaner or a soft non- - metallic bristle brush
as described above.
3. Thoroughly wet all finned surfaces with clean water
using a low velocity garden hose being careful not to
bend fins.
10
CAUTION
CAUTION
C08207

Advertisement

Table of Contents
loading

This manual is also suitable for:

50hcqa0450hcqd0850hcqa0650hcqd0950hcqd1250hcqa07