Application Information
Unit Installation
F Series
Indoor Unit
• Hold the unit and hang it on the hanging rod with the nut and washer.
• Adjust the unit height to 38mm and 30mm respectively depending on series between the indoor unit bottom surface
and the ceiling surface.
• Confirm with a level gauge that the unit is installed horizontally and tighten the nut and bolt to prevent unit falling and
vibration.
• Open the ceiling board along the outer edge of the paper installation template.
2) Outdoor Installation Clearance
Outdoor unit must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth
air flow. Select the coolest possible place where intake air should not hotter than the outside temperature
(Max. 45°C).
RN10/15FV1
C
RN20/25/30/35DV1, RN40/50DY1
C
Dimensions
Minimum Distance, mm
Avoid installing or operating the condensing unit in the environment that is exposed to the
• Sulphide gas (e.g. hot spring areas, oil refinery plant, etc)
12
Ceiling Board
38mm
D
D
300
following substances:
• Oils (including machine oils)
• Salt (e.g. coastal area)
Such substance may lead to the failure of the unit.
C Series
570 (UNIT SIZE)
A
A
A
B
1000
All dimensions are in mm
B
H/2
B
H/2
C
D
300
500