Electric Characteristics - Daikin FTXS-L Series Engineering Data

Split cooling only / heat pump
Hide thumbs Also See for FTXS-L Series:
Table of Contents

Advertisement

Electric Characteristics

10. Electric Characteristics
Indoor Unit
Outdoor Unit
FTXS30LVJU
RKS30LVJU
FTXS36LVJU
RKS36LVJU
FTXS30LVJU
RXS30LVJU
FTXS36LVJU
RXS36LVJU
Symbols:
MCA
: Min. circuit amps (A)
MFA
: Max. fuse amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated load amps (A)
OFM
: Outdoor fan motor
IFM
: Indoor fan motor
W
: Fan motor rated output (W)
FLA
: Full load amps (A)
24
Power Supply
Hz - Volts
Voltage Range
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
COMP
MCA
MFA
RHz
RLA
13.5
19.5
20
66
12.2
84
18.9
19.5
20
90
18.4
18.1
19.5
20
66
16.4
84
20.3
19.5
20
90
18.4
Notes:
1. RLA is based on the following conditions.
Indoor temp. : 80°FDB / 67°FWB (26.7°CDB / 19.4°CWB)
Outdoor temp. : 95°FDB (35°CDB)
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
Split Type Air Conditioners FTXS-L Series
EDUS041129
OFM
IFM
W
FLA
W
FLA
0.39
0.37
200
64
0.35
0.34
0.39
0.37
200
64
0.35
0.34
0.39
0.37
200
64
0.35
0.34
0.39
0.37
200
64
0.35
0.34
3D063167A
3D071271A