Commands - Siemens ATC5300 Manual

Automatic transfer controller
Hide thumbs Also See for ATC5300:
Table of Contents

Advertisement

Å Following table shows meaning of bits of the word at address 207Ah:
Bit
11 ... 15
2.3

Commands

(To be used with function 06)
ADDRESS WORDS
2F00h
2F01h
2F02h
2F03h
2F04h
2F05h
2F06h
2F07h
2F08h
2F0Dh
¿ The following table shows the values to be written to address 2F00h to achieve the
correspondent functions.
Value
À Writing value 01 to the indicated address, the correspondent function will be executed.
Á Writing value AAh to the indicated address, the correspondent function will be executed.
 Writing value FFh to the indicated address, the correspondent function will be executed.
à The following table shows the values to be written to address 2F08h to achieve the
correspondent functions.
ATC5300
Modbus Communication Protocol, Edition 03/2011, A5E02469001-02
0
Line 1 breaker open
1
Line 1 breaker close
2
Line 2 breaker open
3
Line 2 breaker close
4
Global alarm
5
Generator 1 start
6
Generator 2 start
7
ATS ready
8
Load shed
9
Pre-transfer
10
Post-transfer
Not used
1
Operative mode change ¿
1
Device reset (warm boot) À
1
Setup parameters back to factory default À
1
Save parameters in EEPROM Á
1
Hour counter reset Â
1
Operation counters reset Â
1
Event log reset À
1
Save Real time clock setting À
1
Keyboard lock ON / OFF Ã
1
Front panel keystroke simulation Ä
0
Switch to OFF mode
1
Switch to MAN mode
2
Switch to AUT mode
3
Switch to TEST mode
Output Functions Status
FUNCTION
Function
Data Library
2.3 Commands
FORMAT
Unsigned integer
Unsigned integer
Unsigned integer
Unsigned integer
Unsigned integer
Unsigned integer
Unsigned integer
Unsigned integer
Unsigned integer
Unsigned integer
21

Hide quick links: