Weil-McLain SVF Series 1 Manual page 20

Hide thumbs Also See for SVF Series 1:
Table of Contents

Advertisement

SVF
Series 1
COMMERCIAL CONDENSING GAS
Install water piping
Radiant Heating — Zone valve zoning –
secondary (Shown with optional DHW piping)
TM
The
SVF
boiler is ideal for use in radiant heating. The unique heat exchanger
design allows it to work well even in condensing mode. There is no need to
regulate boiler return water temperature in radiant heating applications. The pri-
mary/secondary piping shown ensures the boiler loop will have sufficient flow.
It also avoids applying the high head of the boiler circulator to the zone valves.
1. Apply this configuration for typical radiant heating applications.
2. Size the system piping and circulators to provide the flow and pressure
drop needed.
3. The flow/check valve shown on the boiler outlet piping prevents gravity
circulation in the boiler loop during DHW heating.
Use at least the MINIMUM pipe size shown in Figure 9, page 15
on all boiler loop piping (connecting boiler to and from the primary/
secondary connection, item 21). Primary/secondary piping
shown ensures the boiler loop will have sufficient flow. For other
piping methods, see guidelines on page 15.
High limit in system piping
1. Add the recommended high limit control (Figure 16, item 22) to help ensure
supply water temperature will not exceed the maximum allowable for the
radiant system.
2. Wire the limit control to either the manual reset or automatic reset external
limit circuit of the Control.
Expansion Tank required
1.
Provide a system expansion tank following the guidelines on page 16.
2. DO NOT use a closed-type tank if connecting to a water heater that is equipped
with an automatic vent.
Domestic Hot Water (DHW) tank, if used
1. DHW direct connection—Pipe from the near-boiler piping to the DHW
tank's boiler connections as shown.
2. DHW as zone— Not recommended for this application.
3. System Priority choices:
a. DHW Priority – DHW is priority over space heating. Use Priority
1 for DHW; Priorities 2 and/or 3 for space heating. The control
will not run multiple priorities simultaneously.
b. Space Heating Priority – Space heating is priority over DHW. Use
Priorities 1 and/or 2 for space heating; Priority 3 for DHW. The
control will not run multiple priorities simultaneously.
c. No Priorities – Space heating and DHW can occur simultaneously
at same Supply Max. temperature. Use only if DHW is a zone in
system. Assign DHW and Space heating to same Priority. Do not
use outdoor reset for this application.
Controlling the circulators
1. The control can control up to four circulators (boiler circulator and three
others). Refer to Field wiring, beginning on page 53, for instructions on
wiring to circulators.
TM
1
SVF
boiler
2
Indirect water heater (DHW), if used
3
Boiler relief valve (see page 14 for piping details)
4
Relief valve discharge piping (see page 14 for details)
5
DHW circulator
6
Isolation valves
7
System circulator (see information above for wiring)
8
Diaphragm (or bladder) type expansion tank (see page 16
for piping of closed-type expansion tank, if used)
9
Air separator [with automatic air vent only on systems using diaphragm
(or bladder) type expansion tank]
10 Flow/check valves
11 Purge/drain valves
20
-
FIRED WATER BOILER
(continued)
primary/
Figure 16
See Figure 16.
11
"Caution"
page 15.
2. The factory default settings are: all three inputs are set up for Space
Heating (
lator output. For DHW applications, assign DHW Input(s) to
determined Priority (1, 2, or 3). Priority 1 is defaulted to DHW
for DHW Priority applications.
3. For more than 3-zones, use Weil-McLain WMCR zone Circ
controller.
Legend — Figure 16
12 Boiler circulator
13 Zone valves, when used (zoning may also be done using manifold-mounted valve
actuators).
20 Make-up water supply
21 Primary/secondary connection (tees no more than 8 pipe diameters apart)
22 Optional high limit temperature control, set to protect radiant tubing.
24 System supply and return immersion sensors, at least 6 pipe diameters (but no
more than 3 feet) from boiler connection tees.
25 Systems using high-head pumps may require a bypass pressure regulator to prevent
damage to control valves.
26 External drain/blowdown valve, when used.
33 Strainer, recommended.
— Boiler Manual
Typical radiant heating system piping plus
optional DHW
Radiant manifolds and
6
tubing, typical
6
Valve actuators
optional
25
Do not exceed
8 pipe diameters
21
apart
6
24
24
6
20
8
6
6
11
10
See
NOTE 1
12
6
33
6
10
3
Boiler
1
outlet
4
26
Boiler
return
SVF-3040
Priority 2)
. Each input correlates to its respective circu-
Connect zone valve end switches to a Space Heat-
ing Priority input, (default Priority 2) to use default
settings Connect system circulator to corresponding
output.
Use isolation relays if connecting 3-wire zone valve
end switches to the inputs.
Part number 550-100-200/1018
13
6
Zone valves
optional
13
6
22
9
7
11
5
DHW
outlet
2
Cold
11
water
inlet

Advertisement

Table of Contents
loading

This manual is also suitable for:

Svf 750Svf 1100Svf 1000

Table of Contents