Table 1: IOM47 Physical Features Callouts and Descriptions
Callout
Physical Feature Description
5
Analog Output (AO) Terminal Block, 2 – Analog Outputs. (See
6
24 VAC, Class 2 Supply Power Terminal Block. (See
7
Cover Lift Tab (One of Two). (See
8
Sensor/Actuator (SA) Bus or Field Controller (FC) Bus Terminal Block. (See
9
Binary Input (BI) Terminal Block, 2 – Binary Inputs. (See
10
Universal Input (UI) Terminal Blocks, 6 – Universal Inputs. (See
11
End-of-Line (EOL) Switch. (See
Note: The EOL Switch is located under the controller cover. You must remove the cover to change the EOL switch
position.
12
LED Status Indicators. (See
13
Sensor Actuator (SA) Bus / Field Controller (FC) Bus Port (RJ-12 6-pin Modular Jack). (See
14
BO Terminal Block, 3 – Binary Outputs. (See
Wiring
Observe the following guidelines when wiring a controller:
Risk of Electric Shock: Disconnect the power supply
before making electrical connections to avoid electric
shock.
Mise En Garde: Risque de décharge électrique:
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.
Risk of Property Damage: Do not apply power to the
system before checking all wiring connections. Short
circuited or improperly connected wires may result in
permanent damage to the equipment.
Mise En Garde: Risque de dégâts matériels: Ne pas
mettre le système sous tension avant d'avoir vérifié tous
les raccords de câblage. Des fils formant un court-circuit
ou connectés de façon incorrecte risquent
d'endommager irrémédiablement l'équipement.
Important: Do not exceed the controller electrical
ratings. Exceeding controller electrical
ratings can result in permanent damage to
the controller and void any warranty.
Important: Use copper conductors only. Make all wiring
in accordance with local, national, and
regional regulations.
IOM47 Input/Output Module Installation Instructions
Table
Removing the Controller
Setting the End-of-Line (EOL)
Table
8.)
Table
3.)
Important: Electrostatic discharge can damage
For detailed information on configuring and wiring an
MS/TP Bus, FC bus, and SA bus, refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034).

Terminal Blocks and Bus Ports

See
the controller. Observe the following guidelines when
wiring a controller.

Input and Output Terminal Blocks

All of the input terminal blocks are mounted on the bottom
of the controller and the output terminal blocks are
mounted on the top of the controller. See
information about I/O terminal functions, requirements,
and ratings.

SA/FC Bus Terminal Block

An IOM can be connected to a Sensor/Actuator (SA) bus
or a Field Controller (FC) bus, but not to both buses
simultaneously. The SA/FC bus terminal block is a
removable, 4-terminal plug that fits into a board-mounted
jack.
When connecting the IOM to an FC bus, wire the bus
terminal block plugs on the controller, and the other
controllers in a daisy-chain configuration using 3-wire
twisted, shielded cable as shown in
5
for more information.
Table
3.)
5.)
Cover.)
Table
Table
3.)
Table
3.)
Switch)
controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
Figure 3
for terminal block and bus port locations on
5.)
SA/FC Bus
Port.)
Table 3
for more
Figure
4. See
Table
4