Carrier Debonair 2 Owner's Manual page 19

Non-programmable 2 or 4 pipe systems fan coil thermostat
Hide thumbs Also See for Debonair 2:

Advertisement

About Advanced Features & Operation
DRY CONTACT SWITCH - This feature allows an external device such as a
Central Time Clock, Occupancy Sensor, or a Telephone activated device to
force one or more thermostats into an Unoccupied mode (steps #11 and 12,
page 13).
When the CK1 and R terminals are shorted together, and the thermostat is
programmed for Unoccupied operation (step #12, page 13), the thermostat
will be forced into Unoccupied setpoints and the Unoccupied icon will appear
on the display.
Important Note: For control of multiple thermostats by one source,
refer to 'Potential Phasing Problems' on page 24.
TERMINA L CONNEC TIONS
RS+5
RS
R
G
Y1 G3 W1
G2
C
H2O CK1
Connect wires to a time clock or
other device to force the thermostat
into Occupied 1 or Unoccupied.
18