6. Sound Blankets

Warning
Step
1
Open the sound blanket
(outer).
2
Remove the sound
blanket (top upper).
3
Remove the screw and
slightly push the
partition plate (1) to the
left for easy work.
4
Remove the sound
blanket (outer).
5
Remove the sound
blanket (inner).
Removal Procedure
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Procedure
Sound blanket
(top upper)
Sound blanket
(inner)
Sound blanket
(outer)
(R18077)
Partition plate (1)
Sound blanket
(outer)
(R18055)
Compressor mount
(R23998)
Sound Blankets
Points
The sound blanket is fragile.
Pass the discharge pipe
through it carefully.
The design of the sound
blankets varies depending
on the model.
Since piping ports are torn
easily, remove the sound
blanket carefully.
The sound blanket is fragile.
Be careful of the notches of
the compressor mount (4
locations).