Using A Computer Setpoint (Overriding Controller Setpoint) - Udc2300; Table 5-7 Computer Setpoint Selection; Using A Computer Setpoint - Honeywell UDC2300 Product Manual

Universal digital controller rs422/485 ascii communications option
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

5.6

Using a Computer Setpoint

Setpoint)
Overview
I.D. codes
Shed
60
RS422/485 ASCII Communications Option Product Manual
- UDC2300
You can use a setpoint generated from the computer to override the
setpoint being used by the controller.
The value generated by the computer will have ratio and bias applied by
the controller.
Use the Identifying Code in Table 5-7 to enter the computer setpoint.
Table 5-7
Computer Setpoint Selection
Parameter
Description
Computer Setpoint
125
The computer setpoint override will continue until "SHED" from
communications occurs or the controller is placed into monitor mode
through communications. Doing periodic "SLAVE READS" within the
shed time will allow the override to continue until communication is
stopped and shed time elapses.
0 Shed (code 154) allows the override to continue indefinitely or until the override
is canceled. (See override selection ID code 183.)
When SP is overridden, the upper display will flash "CSP" (provided the
SP Programmer is not enabled) and the lower display will show
"CSXXXX."
(Overriding Controller
Identifying
Format
Code
Code
18
Range or Selection
Value from computer with
Ratio/Bias applied by the
controller. Within the
Setpoint Range Limits in
Engineering Units or
Percent.