4.2
Read Analog Parameters
Introduction
Request format
40
RS422/485 ASCII Communications Option Product Manual
The Analog identifying codes are codes 001 through 125. Each of these
codes is read using the Request and Response formats shown in tables
4-1 and 4-2.
Table 4-1 lists the request format with or without checksum, for Analog
I.D. codes 001 through 125.
Where:
AA
= Station Address
X
= UDC State and Mode (Hex – see "Message Exchange")
NNN
= Identifying Code for Analog Parameter (001 to 125)
CS
= Checksum Value (2 digit hex – see "Checksum")
CR
= Carriage Return
LF
= Line Feed
Table 4-1
Analog Parameter Request Format
Format Type
With Checksum
AA, 4204, X4, NNN, 0, CS CR LF
Without Checksum AA, 0204, X4, NNN, 0, CR LF
Format
10/00