Siemens SIMATIC ET 200SP Manual page 30

Digital input module, di 8x24vdc hf 6es713106bf00-0ca0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Meaning of the LEDs
The tables below explain the meaning of the status and error displays. Corrective measures
for diagnostics alarms can be found in section Diagnostics alarms (Page 32).
DIAG LED
Table 5- 1
DIAG LED
LED channel status/channel error
Table 5- 2
LED channel
PWR LED
Table 5- 3
Digital input module DI 8x24VDC HF (6ES7131-6BF00-0CA0)
Manual, 12/2017, A5E03576305-AE
Error display of the DIAG LED
Meaning
Backplane bus supply of the ET 200SP not OK
Off

Module not ready for operation (no parameters assigned)
Flashes
Module parameters assigned and no module/channel diagnostics
On
Module parameters assigned and module/channel diagnostics
Flashes
Status / error display of the LED channel status / channel error
LED channel
status
error
Off

Off

On
Off

Off

On
On
On
Status display of the PWR LED
PWR LED
Meaning
Missing supply voltage L+
Off

Supply voltage L+ present
On
Meaning
Channel deactivated or process signal = 0
No supply voltage present or
Process voltage > 11 V is present regardless of whether or
not the channel is activated and regardless of whether diag-
nostics was detected
Supply voltage is available and process voltage < 11V is pre-
sent regardless of whether or not the channel is activated and
regardless of whether diagnostics was detected
Channel activated and diagnostics enable was recognized
Interrupts/diagnostics alarms
5.1 Status and error displays
29