Honeywell Experion C300 User Manual page 115

Hide thumbs Also See for Experion C300:
Table of Contents

Advertisement

Plain Text
Soft Failure Conditions
Battery State
Warning
Device Index
Switches Changed
Factory Data Error
ROM Application
Image Checksum
Failure
ROM Boot Image
Checksum Failure
WDT Hardware Error
WDT Refresh
Warning
Critical Task
Watchdog Warning
Uncorrectable
Internal RAM Sweep
Error
Corrected Internal
RAM Sweep Error
Uncorrectable User
RAM Sweep Error
Corrected User RAM
Sweep Error
R301.1
11/06
Parameter Name
BATTERYNOTOKSFTA
B
BCDSWSTS
FACTDATAERR
ROMAPPIMGCHKSMF
AIL
ROMBOOTIMGCHKSM
FAIL
WDTHWFAIL
WDTSWFAIL
TASKHLTHMON
RAMSWEEPERR
RAMSCRUBERRS
BACKUPRAMSWEEPE
RR
BACKUPRAMSCRUBE
RRS
Experion C300 Controller User's Guide
Honeywell
C300 Controller Block
User
Configurable
No
Indicates the status of
CPM battery. Status is
also shown on Main tab of
C300 block.
No
Online diagnostic warning:
Switches broken or
deliberately changed.
No
Online diagnostic error
reading factory data.
No
Online diagnostic error:
ROM application image
CRC.
No
Online diagnostic error:
ROM boot image CRC
No
Online diagnostic error:
Hardware Watchdog
Timer is not responding.
No
Online diagnostic warning:
Watchdog Timer is being
refreshed unacceptably
close to the timout limit.
No
No
Uncorrectable single-bit
errors in Main RAM.
No
Corrected single-bit errors
in Main RAM.
No
Uncorrectable single-bit
errors in Application RAM.
No
Corrected single-bit errors
in Application RAM.
Soft Failures tab
Notes
99

Advertisement

Table of Contents
loading

Table of Contents