Setup And Configuration - Carrier WeatherMaster 48HC04 Series Installation Instructions Manual

Single package rooftop gas heating/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaster 48HC04 Series:
Table of Contents

Advertisement

4.
Press the
(Enter) button to display the value of the
currently displayed item.
5.
Press the ▲ button to increase (change) the displayed
parameter value.
6.
Press the ▼ button to decrease (change) the displayed
parameter value.
NOTE: When values are displayed, pressing and holding the
▲or ▼ button causes the display to automatically increment or
decrement.
1.
Press the
(Enter) button to accept the displayed value
and store it in nonvolatile RAM. "CHANGE STORED"
displays.
2.
Press the
(Enter) button to return to the current menu
parameter.
3.
Press the
(Menu Up/Exit) button to return to the previ-
ous menu.
Menu Structure
Table 10 illustrates the complete hierarchy of menus and parame-
ters for the EconoMi$er
®
X system.
The Menus in display order are:
STATUS
SETPOINTS
SYSTEM SETUP
ADVANCED SETUP
MENU
PARAMETER
ECON AVAIL
ECONOMIZING
OCCUPIED
HEAT PUMP
COOL Y1—IN
COOL Y1—OUT
STATUS
COOL Y2—IN
COOL Y2—OUT
MA TEMP
DA TEMP
OA TEMP
Table 10 — W7220 Menu Structure*
PARAMETER
PARAMETER
DEFAULT
RANGE AND
VALUE
INCREMENT
NO
YES/NO
NO
YES/NO
NO
YES/NO
COOL
N/A**
HEAT
OFF
ON/OFF
OFF
ON/OFF
OFF
ON/OFF
OFF
ON/OFF
_ _ . _ °F
–40°F to 150°F
(or _ _ . _ °C)
(–40°C to 66°C)
_ _ . _ °F
–40°F to 150°F
(or _ _ . _ °C)
(–40°C to 66°C)
_ _ . _ °F
–40°F to 140°F
(or _ _ . _ °C)
(–40°C to 60°C)
32
CHECKOUT
ALARMS
NOTE: Some parameters in the menus use the letters MA or
MAT, indicating a mixed air temperature sensor location before
the cooling coil. This unit application has the control sensor locat-
ed after the cooling coil, in the fan section, where it is designated
as (Cooling) Supply Air Temperature or SAT sensor.

SETUP AND CONFIGURATION

Before being placed into service, the W7220 Economizer mod-
ule must be set up and configured for the installed system.
IMPORTANT: During setup, the economizer module is
live at all times.
The setup process uses a hierarchical menu structure that is
easy to use. Press the ▲ and ▼ arrow buttons to move forward
and backward through the menus and press the button to select
and confirm setup item changes.
Time-Out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status items.
Each Status items displays in turn and cycles to the next item
after 5 seconds.
EXPANDED PARAMETER NAME
FIRST STAGE COOLING DEMAND (Y1–IN)
YES = economizing available; the system can use outside air for
free cooling when required
FIRST STAGE COOLING RELAY OUTPUT
YES = outside air being used for first stage cooling
OCCUPIED
YES = OCC signal received from space thermostat or unitary
controller
YES = 24 vac on terminal OCC
NO = 0 vac on terminal OCC
HEAT PUMP MODE
Displays COOL or HEAT when system is set to heat pump
(Non-conventional)
FIRST STAGE COOLING DEMAND (Y1-IN)
Y1–I signal from space thermostat or unitary controller for cooling
stage 1.
ON = 24 vac on terminal Y1–I
OFF = 0 vac on terminal Y1–I
FIRST STAGE COOLING RELAY OUTPUT
Cool stage 1 Relay Output to stage 1 mechanical cooling
(Y1–OUT terminal)
SECOND STAGE COOLING DEMAND (Y2–IN)
Y2–I signal from space thermostat or unitary controller for
second stage cooling.
ON = 24 vac on terminal Y2–I
OFF = 0 vac on terminal Y2–I
SECOND STAGE COOLING RELAY OUTPUT
Cool Stage 2 Relay Output to mechanical cooling
(Y2–OUT terminal)
SUPPLY AIR TEMPERATURE, Cooling Mode
Displays value of measured mixed air from MAT sensor.
Displays _ _ . _ F if not connected, short or out of range.
DISCHARGE AIR TEMPERATURE, after Heating section
Displays when Discharge Air Sylk Bus sensor is connected and
displays measured discharge temperature.
Displays _ _ . _F if sensor sends invalid value, if not connected,
short or out of range.
OUTSIDE AIR TEMP
Displays measured value of outdoor air temperature.
Displays _ _ . _F if sensor sends invalid value, short or out of
range.
Notes