Economizer Module Wiring Details - Carrier WeatherMaster 48HC04 Series Installation Instructions Manual

Single package rooftop gas heating/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaster 48HC04 Series:
Table of Contents

Advertisement

Storage Temperature
–40°F to 150°F (–40°C to 65°C)
Shipping Temperature
–40°F to 150°F (–40°C to 65°C)
Relative Humidity
5% to 95% RH non-condensing

ECONOMIZER MODULE WIRING DETAILS

Use Fig. 52 and Tables 6 and 7 to locate the wiring terminals
for the Economizer module.
NOTE: The four terminal blocks are removable. Slide out each
terminal block, wire it, and then slide it back into place.
MAT
MA
MAT
MA
OAT
OA
OAT
OA
S-BUS
SB
SB
S-BUS
SB
SB
SB
SB
V
IAQ 2-10
C
R
IAQ COM
IAQ 24V
V
C
ACT 2-10
R
NA
ACT COM
ACT 24V
50040839-001
Rev. G
Fig. 52 — W7220 Wiring Terminals
NA
AUX2-
NA
OCC
A2
OC C
E-GND
EXH1
EX
A1
AUX1-O
Cert
Product
California Title 24, Part 6
HJW10
www.energy.ca.gov
Y2-
Y2I
Y2O
Y2-O
Y1I
Y1-
Y1O
Y1-O
C
R
C
R
50048848-002
Rev. A
Table 6 — Economizer Module - Left Hand Terminal
LABEL
TYPE
Top Left Terminal Block
MAT
20k NTC
MAT
and COM
OAT
20k NTC
OAT
and COM
S-BUS
S-BUS
S-BUS
(Sylk* Bus)
Bottom Left Terminal Block
IAQ 2-10
2-10 vdc
IAQ COM
COM
IAQ 24V
24 vac
ACT 2-10
2-10 vdc
ACT COM
COM
ACT 24v
24 vac
*Sylk is a trademark of Honeywell International Inc.
Table 7 — Economizer Module - Right Hand Terminal
LABEL
TYPE
Top Right Terminal Blocks
AUX2 I
24 vac IN
OCC
24 vac IN
E-GND
E-GND
EXH1
24 vac OUT Exhaust Fan 1 Output
AUX1 O
24 vac OUT
Bottom Right Terminal Blocks
Y2-I
24 vac IN
Y2-O
24 vac OUT
Y1-I
24 vac IN
Y1-O
24 vac OUT
C
COM
R
24 vac
S-Bus Sensor Wiring
The labels on the sensors and controller are color coded for
ease of installation. Orange labeled sensors can only be wired
to orange terminals on the controller. Brown labeled sensors
can only be wired to S-bus (brown) terminals. Use Fig. 53 and
Table 8 to locate the wiring terminals for each S-Bus sensor.
Use Fig. 52 and Table 8 to locate the wiring terminals for each
enthalpy control sensor.
30
Blocks
DESCRIPTION
Mixed Air Temperature Sensor (Polarity
Insensitive Connection)
Outdoor Air Temperature Sensor (Polarity
Insensitive Connection)
Enthalpy Control Sensor
(Polarity Insensitive Connection)
Air Quality Sensor Input (e.g. CO
sensor)
Air Quality Sensor Common
Air Quality Sensor 24 vac Source
Damper Actuator Output (2-10 vdc)
Damper Actuator Output Common
Damper Actuator 24 vac Source
Blocks
DESCRIPTION
The first terminal is not used.
Shut Down (SD) or HEAT (W)
Conventional only
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
Occupied/Unoccupied Input
Programmable:
Exhaust fan 2 output
or
ERV
or
System alarm output
Y2 in - Cooling Stage 2 Input from space
thermostat
Y2 out - Cooling Stage 2 Output to stage
2 mechanical cooling
Y1 in - Cooling Stage 2 Input from space
thermostat
Y1 out - Cooling Stage 2 Output to stage
2 mechanical cooling
24 vac Common
24 vac Power (hot)
2