Introduction; Hardware Installation; Wiring Diagram - Watchguard WGAP864 Quick Installation Manual

Hide thumbs Also See for WGAP864:
Table of Contents

Advertisement

Introduction

WGAP864 is a professional alarm panel. It covers hundreds of features and thousands of
installation combinations. This Quick Installation Guide summarizes the most commonly
used features for installers. Please refer to the Installer Manual for those functions not
mentioned in this guide for more detailed information.

Hardware Installation

EOL (End-Of-Line) resistor: End-Of-Line resistor has to be installed so that the electrical
current will complete a loop from the alarm panel zone input to the sensor. The alarm panel
monitors the current flow through the loop. If someone tries to tamper by cutting or
shorting circuit the loop wiring, the alarm panel will detect the current change and will
trigger the alarm panel.
For normal zones, the EOL resistor is 3k3 ohm.
For tamper zones, the EOL resistor is 4k7 ohms for the sensor output and 12K ohms for the
tamper switch. The combined resistance of the two completed circuits is approx. 3k3 ohms.
Please refer to the wiring diagram for connection.

Wiring Diagram

Copyright © Cornick Pty. Ltd. 2018
Page 1