Supply Air Temperature (Sat) Sensor; Outdoor Air Temperature (Oat) Sensor - Bryant 551J*07A/G Series Installation Instructions Manual

Single package rooftop cooling only sizes 07, 08, 09, 11 and 12 with puronr (r--410a) refrigerant
Table of Contents

Advertisement

BACnet OBJECT
POINT NAME
Space Temp / Zone Temp
Supply Air Temperature
Outside Air Temperature
Space Temperature Offset Pot
Safety Chain Feedback
(1)
Compressor Safety Status
Fire Shutdown Status
Enthalpy Status
Humidistat Input Status
Zone Temperature
Indoor Air CO2
Outdoor Air CO2
Space Relative Humidity
(2)
Supply Fan Status
(2)
Filter Status
(2)
Door Contact
door_contact_status
(2)
Remote Occupancy input
occ_contact_status
(2)
IGC input
Economizer Output
Supply Fan VFD
Supply Fan Relay
Cool 1 Relay State
Cool 2 Relay State
Cool 3 Relay State
Heat 1 Relay State
Heat 2 Relay State
Power Exhaust Relay State
Dehumidification Relay
LEGEND
AI
---
Analog Input
AO
---
Analog Output
BI
---
Binary Input
BO
---
Binary Output
(1)
Safety Chain Feedback: 24Vac required at this terminal to provide "Run Enable" status. See Input/Output section for additional instructions.
(2)
These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Configuration Section for wiring and setup instructions.
(3)
Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5--- 5 = J1--- 2 are used for field installation.
(4)
Refer to the input configuration and accessory sections of the Factory Installed Option RTU Open Controls, Start ---Up, Operation and Troubleshooting manual for more detail.
The RTU Open controller requires the use of a Bryant
space sensor. A standard thermostat cannot be used with
the RTU Open system.
Supply Air Temperature (SAT) Sensor —
On FIOP- - equipped 551J unit, the unit is supplied with a
supply- - air temperature (SAT) sensor (33ZCSENSAT). This
sensor is a tubular probe type, approx 6- - inches (152 mm) in
length. It is a nominal 10- - k ohm thermistor.
The SAT is factory- - wired. The SAT probe is wire- - tied to
the supply- - air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re- - position the sensor in the flange of the supply- - air
opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/
Use two field- - supplied, self- - drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 43.
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory- - mounted in the EconoMi$er2 (FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
Table 18 – RTU Open Controller Inputs and Outputs
TYPE OF I/O
NAME
zone_temp
AI (10K Thermistor)
sa_temp
AI (10K Thermistor)
oa_temp
AI (10K Thermistor)
stpt_adj_offset
AI (100K Potentiometer)
safety_status
BI (24 VAC)
comp_status
BI (24 VAC)
firedown_status
BI (24 VAC)
enthalpy_status
BI (24 VAC)
humstat_status
BI (24 VAC)
n/a
n/a
CONFIGURABLE INPUTS
iaq
AI (4---20 mA)
oaq
AI (4---20 mA)
space_rh
AI (4---20 mA)
sfan_status
BI (24 VAC)
filter_status
BI (24 VAC)
BI (24 VAC)
BI (24 VAC)
igcovr_status
BI (24 VAC)
econ_output
AO (4---20mA)
vfd_output
AO (2---10Vdc)
sfan
BO Relay (24VAC, 1A)
comp_1
BO Relay (24VAC, 1A)
comp_2
BO Relay (24VAC, 1A)
comp_3
BO Relay (24VAC, 1A)
heat_1
BO Relay (24VAC, 1A)
heat_2
BO Relay (24VAC, 1A)
pexh
BO Relay (24VAC, 1A)
dehum
BO Relay (24VAC, 1A)
- - in. hole in the flange or duct.
2
CONNECTION PIN NUM-
BER(S)
DEDICATED INPUTS
J20---1 and 2
J2---1 and 2
J2---3 and 4
J20---3 and 4
J1---9
J1---2
J1---10
J2---6 and 7
J5---7 and 8
J13---1---4
(4)
J4---2 and 3 or J4---5 and 6
J5---1 and 2 or J5---3 nd 4,
(3)
J5---5 and 6 or J5---7 and 8
OUTPUTS
J2---5
J22---1 and 2
J1---4
J1---8
J1---7
J11---5 and 6
J1---6
J1---5
J11---2 and 3 (N.O.)
J11---7 and 8 (N.O.)
SUPPLY AIR
TEMPERATURE
SENSOR
Fig. 43 - - Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
41
CHANNEL DESIGNATION
Analog Input 10
Analog Input 6
Analog Input 7
Analog Input 11
Binary Input 4
Binary Input 3
Binary Input 5
Binary Input 8
Binary Input 9
Rnet
Analog Input 2
Analog Input 1
Analog Input 10
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 9. Mandatory input on gas heat units.
Analog Output 1
Analog Output 2
Binary Output 1 (G)
Binary Output 5 (Y1)
Binary Output 4 (Y2)
Binary Output 7 (Y3)
Binary Output 3 (W1)
Binary Output 2 (W2)
Binary Output 8 (PE)
Binary Output 6
SUPPLY AIR
RETURN AIR
ROOF
CURB
C08200