For EN50131-1 compliant installations, the following programming options shall be set as described.
Supervision Heartbeat (required for ATS4 and ATS5):
[851][004] set to 0087h (135s heartbeat).
l
NOTE: The compatible receiver at ARC location shall have supervision window programmed for 1800s (ATS4) or 180s (ATS
5).
[851][005] options 1 and 3 shall be enabled
l
Test transmission (required for ATS3):
[851] System test options [026] and [027] shall be enabled (FF) for the communication paths available.
l
[851][124] and [125] shall be programmed with time of day for test transmission and 1440 minutes (24h) for test trans-
l
mission cycle
Configuration of communication paths (all ATS classes)
[300][001] select option 02 for auto routing (this will allow transmission of the events over all available communication
l
paths in the system)
[380] enable option 5 (YES) for parallel transmission over all available communication paths (if redundant configuration is
l
desired)
[382] enable option 5 (YES) this will enable Alternate communicator
l
[384] enable the desired back-up configuration (receiver 2 back-up for receiver 1 or receiver 3 back-up for receiver 1).
l

Technical Specifications, Ratings and Compatibility

Model
Power Supply Ratings
Input Voltage
Current Consumption
Current
Environmental Specifications
Operating Temperature
Humidity
Mechanical Specifications
Board Dimensions (mm)
Weight (grams) with bracket
Communicator
Receiver/Panel
3G2080(R)
Receiver
TL2803G(R)
Panel
NOTE: Enter [*][8][Installer Code][900] at keypad to view the panel version number.

Communicator Installation Configuration

This Ethernet communicator shall be installed by service persons only (service person is defined as a person having the appro-
priate technical training and experience necessary to be aware of hazards to which that person may be exposed to in

EN50131-1 Installation Requirements

Table 1: Communicator Ratings
10.8-12.5 VDC. Power is supplied from the panel's PC-Link header or a
powered by either an HSM2204 or an HSM2300. Refer to the PCL-422
Table 2: Compatible Receivers and Panels
Sur-Gard System I-IP Receiver, version 1.13+
l
Sur-Gard System II Receiver, version 2.10+
l
Sur-Gard SG-DRL3-IP, version 2.30+ (for Sur-Gard System III Receiver)
l
Sur-Gard SG-DRL4-IP version 1.20+ (for Sur-Gard System IV Receiver)
l
Sur-Gard SG-DRL5-IP version 1.00+ (for Sur-Gard System 5 Receiver)
l
HS2016
l
HS2032
l
HS2064
l
HS2128
l
PCL-422 module in remote cabinet installations. In remote cabinet
installations, the PCL-422 module located with the communicator is
installation instructions for details.
100mA @ 13.66V
5% ~ 93% relative humidity, non-condensing
Description
5
TL280(R)
-10°C to 55°C
100 × 150 × 15
290