Siemens SIMATIC TIWAY 1 User Manual page 176

Unilink host adapter
Hide thumbs Also See for SIMATIC TIWAY 1:
Table of Contents

Advertisement

ERROR CODES AND DIAGNOSTICS
6.4.4
External I/O Loopback Test
There is a special diagnostic test for the Input/Output Points. This test is active
when Positions 9 and 10 of Dipswitch 2 are up. To run this test, perform the
following steps.
1. Install a 20.0 to 30.0 VDC power supply to the output power terminal
(#3) shown in Figure 6–5.
2. Using a 22 AWG wire, connect the input point terminal (#1) to the
output point terminal (#5).
3. Using another 22 AWG wire, connect the input point return (#2) to the
output point return (#4).
4. Install the loopback connectors provided with the adapter to Port 3 and
Port 4.
5. Apply power to the adapter.
6. Set Positions 9 and 10 of Dipswitch 2 up.
7. Press the reset switch.
Pin
1 – Input
2 – Input Return
3 – Power
4 – Output Return
5 – Output
Figure 6–5 External I/O Loopback Test Connections
If the External I/O loopback test fails, the pattern shown in Figure 6–4 will be
displayed on the LEDs. Check the connections shown in Figure 6–5 and retest.
If the test continues to fail, return the unit for repair.
D
I
R
R
O
C
N
T
T
U
+
N
N
T
3
1
2
4
5
6–13
UNILINK HOST ADAPTER
USER MANUAL

Advertisement

Table of Contents
loading

Table of Contents