5.4.3
Report HIU Configuration — 12
The REPORT HIU CONFIGURATION command reports the values for the
HIU options specified with the CONFIGURE HIU command.
Command:
Response:
Usage:
Modes:
Parameters:
dddd
MSB
1 2 3 4
ff
oo
vvvv
UNILINK HOST ADAPTER
USER MANUAL
HOST COMMAND SET REFERENCE
12
12 dddddddd ff 01 vvvv 02 vvvv 03 vvvv
CONFIGURATION
MHIU, HIU
The current values for Dipswitch 1 and Dipswitch 2 in the most
significant word and least significant word respectively. The
position values are right-justified in each word as shown in
Figure 5–5. A bit set to one indicates the corresponding switch is
up.
WORD #1
5
6
7
8
9
10
11
12 13
1
2
3 4
5
6
7
8
U
P
Dipswitch 1
Figure 5–5 Dipswitch Values Bit Map
A flag indicating that the CONFIGURE HIU command has been
processed when set to one. In multiprocessing environments, the
tasks can check this flag to determine whether they can start
issuing initiation, operation, and termination commands or not.
The option number ranging from 01 to 03. All four option/value
pairs will be returned.
The parameter values described in the CONFIGURE HIU
command.
LSB
MSB
14
15
1 2 3 4
5
6
7
9 10
1
2
U
P
5–24
WORD #2
LSB
8
9
10
11
12 13
14
15
3 4
5
6
7
8
9 10
Dipswitch 2