Heat pump controller – multistage
Table of Contents

Advertisement

Description
Address
DMPR POS
{49}
MTR1 POS
{49}
DO 8
{50}
FAN
{50}
MTR TIMING
51
MTR1 TIMING
51
AI 3
{52}
AI 4
{53}
AOV 2
{54}
DI 3
{55}
DMPR ROT ANG
56
DPR1 ROT ANG
56
DI 4
{57}
MTR SETUP
58
DO DIR.REV
59
Siemens Building Technologies, Inc.
Application
2583, 2584
Current position of the damper motor in percent of full travel.
This value is calculated based on motor run time.
2590
Current position of the damper motor in percent of full travel.
This value is calculated based on motor run time. See
MTR1 TIMING.
2590
Digital output 8 controls a 24 Vac load with an ON or OFF
status.
2583, 2584
Digital output used to control the fan. ON indicates the DO is
energized; OFF indicates the DO is de-energized.
2583, 2584
Time required for the damper actuator to travel from full
closed to the full open position.
2590
Time required for the Motor 1 actuator to travel from full
closed to the full open position.
2583, 2584, 2590
Spare analog input, switch selectable to be 0-10V or 4-
20mA (consult your Siemens Building Technologies
representative). Or, spare DI dry contact, see DI 3. The
physical input can not be used for both analog and digital
input at the same time.
2583, 2584, 2590
Spare anolog input, 10K Ω thermistor. Or, spare DI dry
contact, see DI 4. The physical input can not be used for
both analog and digital input at the same time.
2583, 2584, 2590
Analog output 2 controls a 0 to 10V signal.
2583, 2584, 2590
Actual status of a contact connected to the controller at
Dl 3. ON indicates that the contact is closed; OFF indicates
that the contact is open. When a contact is connected at Dl
3, Al 3 is not available. See AI 3. The physical input can not
be used for both analog and digital input at the same time.
2583, 2584
Number of degrees the damper is free to travel.
2590
Number of degrees the damper is free to travel.
2583, 2584, 2590
Actual status of a contact connected to the controller at
Dl 4. ON indicates that the contact is closed; OFF indicates
that the contact is open. When a contact is connected at Dl
4, Al 4 is not available. See AI 4. The physical input can not
be used for both analog and digital input at the same time.
2583, 2584, 2590
Configuration setup code for Motors 1 and 2. This enables
the motors individually and sets each motor to be either
direct or reverse acting.
NOTE: When a motor is enabled, its associated DOs are
enabled.
2583, 2584, 2590
Configuration setup code for DOs. Allows the DOs to be
direct or reverse acting (enabled equals energized or
disabled equals de-energized).
Point Database