Siemens BACNET 125-699 Owner's Manual page 29

Heat pump controller – multistage
Table of Contents

Advertisement

Description
Address
DAY.NGT
{29}
CLG CMP1 ON
30
CLG CMP1 OFF
31
CLG1 MlN OFF
32
CLG1 MlN ON
33
CLG CMP2 ON
34
CMP3 ON
34
CLG CMP2 OFF
35
CMP3 OFF
35
CLG2 MIN OFF
36
CMP3 MlN OFF
36
CLG2 MlN ON
37
CMP3 MlN ON
37
DAMPER TYPE
38
AO DIR.REV
39
AOV1
{40}
Siemens Building Technologies, Inc.
Application
2583, 2584, 2590
Indicates the mode in which the controller is operating.
Day temperature setpoints are used in day mode.
Night temperature setpoints are used in night mode. This
point is normally set by the field panel.
2584
Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 1 to turn ON.
Actual turn on is subject to the CLG1 MlN OFF time being
expired.
2584
Value, in percent, that the cooling temperature control loop
output must go below for cooling compressor 1 to turn OFF.
Actual turn off is subject to the CLG1 MlN ON time being
expired.
2584
Minimum time, in minutes, that cooling compressor 1 will
remain OFF before turning ON.
2584
Minimum time, in minutes, that cooling compressor 1 will
remain ON before turning OFF.
2584
Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 2 to turn ON.
Actual turn on is subject to the CLG 2 MIN OFF time being
expired.
2583
Value, in percent, that the active temperature control loop
output must exceed for compressor 3 to turn ON. Actual
turn on is subject to the CMP3 MlN OFF time being expired.
2584
Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 2 to turn OFF.
Actual turn off is subject to the CLG2 MIN ON time being
expired.
2583
Value, in percent, that the active temperature control loop
output must go below for compressor 3 to turn OFF. Actual
turn off is subject to the CMP3 MlN ON time being expired.
2584
Minimum time, in minutes, that cooling compressor 2 will
remain OFF before turning ON.
2583
Minimum time, in minutes, that compressor 3 will remain
OFF before turning ON.
2584
Minimum time, in minutes, that cooling compressor 2 will
remain ON before turning OFF.
2583
Minimum time, in minutes, that compressor 3 will remain ON
before turning OFF.
2583, 2584
FLOAT indicates that a floating control damper is used.
SPRING indicates that a spring return damper is used.
Valid input: FLOAT or SPRING.
2583, 2584
Configuration setup code for AO. Allows the AO to be direct
(normally closed) or reverse acting (normally open).
2583, 2584, 2590
Analog output 1 controls a 0 to 10V signal.
Point Database
Description