General
CAUTION
Provisions for component cooling must be made at the installation site. Power loss data are
given in the technical specifications.
Assignment of sine-wave filter and Power Module
Table 2- 1
6SL3310-1GE32-1AAx
6SL3310-1GE32-6AAx
6SL3310-1GE33-1AAx
6SL3310-1GE33-8AAx
6SL3310-1GE35-0AAx
6SL3310-1GF31-8AAx
6SL3310-1GF32-2AAx
Restrictions
The following restrictions must be taken into account when a sine-wave filter is used:
● The output frequency is limited to max. 115 Hz (at 500 – 600 V) and 150 Hz (at 380 – 480
● The modulation type is permanently set to space-vector modulation without
● The maximum output frequency is limited to 85% of the input frequency.
● Maximum permissible motor cable lengths:
● During commissioning, the pulse frequency rises to double the factory setting. This
Note
If a filter cannot be parameterized (p0230 ≠ 3) during commissioning, then no provision is
made for this SIEMENS sine-wave filter for the SINAMICS G130.
12
Assignment of sine-wave filter and Power Module
Power Module
V).
overmodulation.
– Unshielded cable: max. 450 m
– Shielded cable: max. 300 m
induces current derating, which must be applied to the built-in units' rated currents listed
in the technical specifications.
Unit rating of the Power Module
Line voltage 380 – 480 V 3 AC
110 kW
132 kW
160 kW
200 kW
250 kW
Line voltage 500 – 600 V 3 AC
110 kW
132 kW
Suitable sine-wave filter
6SL3000-2CE32-3AA0
6SL3000-2CE32-3AA0
6SL3000-2CE32-8AA0
6SL3000-2CE33-3AA0
6SL3000-2CE34-1AA0
6SL3000-2CF31-7AA0
6SL3000-2CF31-7AA0
Operating Instructions, 05/2010, A5E00992420A