9.3 Configuring the Detector
1. After completion of the startup sequence,
press the "p" button for a few seconds to
select the setup menu.
2. Enter the passcode (if necessary).
3. Use the "p" or "q" buttons to select the
setup menu " " icon. Press the "P" to accept.
4. Use the "p"or "q"buttons to select the set
alarms " ALm" submenu. Press "P" to
accept.
5. The flashing gas ID code and the gas cylinder
and alarms icon " '' will appear.
6. Use the "p" or "q" buttons to change the
gas ID number to that of the target gas. Press
"P"to accept.
7. Continue to accept or change the rest of
the alarm settings. For further details on
these settings, refer to the Midas Operating
Instructions (part number MIDAS-A-001).
8. Press "P" to update all changes ("UPdt" will
be displayed).
9. Press "X" twice to return to normal operation.
After applying power, verify that the sensor
cartridge ID and gas ID are appropriate for the
target gas. See
Appendix B
Refer to
Section 7.2.2
setting the gas ID code.
The Midas gas detector automatically detects the
pyrolyzer module and provides the necessary power
and signaling for the device.
for gas ID codes.
for the procedure for